-- == OG-STATUSv2-MIB:                                                  ==
-- == Opengear status Management Information Base                    ==
-- ==                                                                 ==
-- == (c) Copyright 2013-2017 Opengear Inc.                                ==
-- =====================================================================

OG-STATUSv2-MIB DEFINITIONS ::= BEGIN

IMPORTS
	opengear
		FROM OG-SMI-MIB
	MODULE-IDENTITY, NOTIFICATION-TYPE, OBJECT-TYPE
		FROM SNMPv2-SMI
	Integer32, Unsigned32, Counter32, Counter64
		FROM SNMPv2-SMI
	MODULE-COMPLIANCE, NOTIFICATION-GROUP, OBJECT-GROUP
		FROM SNMPv2-CONF
	DateAndTime, DisplayString
		FROM SNMPv2-TC;

ogStatus2 MODULE-IDENTITY
	LAST-UPDATED "201702030000Z"
	ORGANIZATION "Opengear Inc."
	CONTACT-INFO
		"Opengear Inc.
		 630 West 9560 South, Suite A,
		 Sandy, UT 84070
		 support@opengear.com"
	DESCRIPTION
		"Opengear extended status and alert MIB"
	REVISION "201702030000Z"
	DESCRIPTION
		"Add CLI session alert."
	REVISION "201608260000Z"
	DESCRIPTION
		"Correct Power Supply table and values."
	REVISION "201401280000Z"
	DESCRIPTION
		"Initial revision"
       ::= { opengear 17 }

ogSystem OBJECT IDENTIFIER
       ::= { ogStatus2 1 }

ogFirmwareVersion OBJECT-TYPE
	SYNTAX DisplayString (SIZE (0..64))
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The current device firmware."
	::= { ogSystem 1 }

ogSerialNumber OBJECT-TYPE
	SYNTAX DisplayString (SIZE (0..64))
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The current serial number (if applicable)."
	::= { ogSystem 2 }

ogSerialPortTable OBJECT-TYPE
	SYNTAX  SEQUENCE OF SerialPortEntry
	MAX-ACCESS not-accessible
	STATUS     current
	DESCRIPTION
           "The devices serial port status table."
	::= { ogStatus2 2 }

ogSerialPortEntry OBJECT-TYPE
	SYNTAX SerialPortEntry
	MAX-ACCESS not-accessible
	STATUS current
	DESCRIPTION
		"A serial port status entry."
	INDEX { ogSerialPortIndex }
	::= { ogSerialPortTable 1 }

SerialPortEntry ::= SEQUENCE {
        ogSerialPortIndex         Integer32,
        ogSerialPortLabel         DisplayString,
        ogSerialPortSpeed         Integer32,
        ogSerialPortDataBits      Integer32,
        ogSerialPortParity        INTEGER,
        ogSerialPortStopBits      INTEGER,
        ogSerialPortFlowControl   INTEGER,
        ogSerialPortMode          INTEGER,
        ogSerialPortLogLevel      INTEGER,
 	ogSerialPortRxBytes       Counter64,
 	ogSerialPortTxBytes       Counter64,
 	ogSerialPortFramingErrors Counter64,
 	ogSerialPortParityErrors  Counter64,
 	ogSerialPortOverrunErrors Counter64,
 	ogSerialPortBreaks        Counter64,
        ogSerialPortDCD           INTEGER,
        ogSerialPortDTR           INTEGER,
        ogSerialPortDSR           INTEGER,
        ogSerialPortCTS           INTEGER,
        ogSerialPortRTS           INTEGER
}

ogSerialPortIndex OBJECT-TYPE
	SYNTAX Integer32 (0..65535)
	MAX-ACCESS not-accessible
	STATUS current
	DESCRIPTION
		"Index within the serial port table of this status"
	::= { ogSerialPortEntry 1 }

ogSerialPortLabel OBJECT-TYPE
	SYNTAX DisplayString (SIZE (0..64))
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"Serial port descriptive name"
	::= { ogSerialPortEntry 2 }

ogSerialPortSpeed OBJECT-TYPE
	SYNTAX Integer32
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"Serial port speed in bits per second"
	::= { ogSerialPortEntry 3 }

ogSerialPortDataBits OBJECT-TYPE
	SYNTAX Integer32
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"Serial port character size"
	::= { ogSerialPortEntry 4 }

ogSerialPortParity OBJECT-TYPE
        SYNTAX INTEGER {
            none(1),
            odd(2),
            even(3),
            mark(4),
            space(5)
        }
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"Serial port parity"
	::= { ogSerialPortEntry 5 }

ogSerialPortStopBits OBJECT-TYPE
	SYNTAX INTEGER {
	    one(1),
	    two(2),
	    oneAndAHalf(3)
	}
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"Serial port number of stop bits"
	::= { ogSerialPortEntry 6 }

ogSerialPortFlowControl OBJECT-TYPE
	SYNTAX INTEGER {
	    none(1),
	    hardware(2),
	    software(3)
	}
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"Serial port flow control type"
	::= { ogSerialPortEntry 7 }

ogSerialPortMode OBJECT-TYPE
	SYNTAX INTEGER {
	    none(1),
	    console(2),
	    sdt(3),
	    terminal(4),
	    bridge(5)
	}
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"Serial port operational mode type"
	::= { ogSerialPortEntry 8 }

ogSerialPortLogLevel OBJECT-TYPE
	SYNTAX INTEGER {
	    disabled(1),
	    connect(2),
	    inputAndOutput(3),
	    inputOnly(4),
	    outputOnly(5)
	}
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"Serial port logging level"
	::= { ogSerialPortEntry 9 }

ogSerialPortRxBytes OBJECT-TYPE
	SYNTAX Counter64
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"Serial port bytes received"
	::= { ogSerialPortEntry 10 }

ogSerialPortTxBytes OBJECT-TYPE
	SYNTAX Counter64
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"Serial port bytes transmitted"
	::= { ogSerialPortEntry 11 }

ogSerialPortFramingErrors OBJECT-TYPE
	SYNTAX Counter64
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"Serial port framing error total."
	::= { ogSerialPortEntry 12 }

ogSerialPortParityErrors OBJECT-TYPE
	SYNTAX Counter64
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"Serial port parity error total."
	::= { ogSerialPortEntry 13 }

ogSerialPortOverrunErrors OBJECT-TYPE
	SYNTAX Counter64
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"Serial port Overrun Error total."
	::= { ogSerialPortEntry 14 }

ogSerialPortBreaks OBJECT-TYPE
	SYNTAX Counter64
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"Serial port break total"
	::= { ogSerialPortEntry 15 }

ogSerialPortDCD OBJECT-TYPE
        SYNTAX INTEGER {
            on(1),
            off(2)
        }
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The status of the DCD signal."
	::= { ogSerialPortEntry 16 }

ogSerialPortDTR OBJECT-TYPE
        SYNTAX INTEGER {
            on(1),
            off(2)
        }
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The status of the DTR signal."
	::= { ogSerialPortEntry 17 }

ogSerialPortDSR OBJECT-TYPE
        SYNTAX INTEGER {
            on(1),
            off(2)
        }
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The status of the DSR signal."
	::= { ogSerialPortEntry 18 }

ogSerialPortCTS OBJECT-TYPE
        SYNTAX INTEGER {
            on(1),
            off(2)
        }
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The status of the CTS signal."
	::= { ogSerialPortEntry 19 }

ogSerialPortRTS OBJECT-TYPE
        SYNTAX INTEGER {
            on(1),
            off(2)
        }
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The status of the RTS signal."
	::= { ogSerialPortEntry 20 }

ogSerialUserTable OBJECT-TYPE
	SYNTAX  SEQUENCE OF SerialUserEntry
	MAX-ACCESS not-accessible
	STATUS     current
	DESCRIPTION
           "This entity's serial port users table."
	::= { ogStatus2 3 }

ogSerialUserEntry OBJECT-TYPE
	SYNTAX SerialUserEntry
	MAX-ACCESS not-accessible
	STATUS current
	DESCRIPTION
		"A user logged in on the serial port"
	INDEX { ogSerialUserIndex }
	::= { ogSerialUserTable 1 }

SerialUserEntry ::= SEQUENCE {
        ogSerialUserIndex      Integer32,
        ogSerialUserStartTime  DateAndTime,
        ogSerialUserPort       Integer32,
        ogSerialUserLabel      DisplayString,
        ogSerialUserName       DisplayString
}

ogSerialUserIndex OBJECT-TYPE
	SYNTAX Integer32 (0..65535)
	MAX-ACCESS not-accessible
	STATUS current
	DESCRIPTION
		"Index within the serial port active users table"
	::= { ogSerialUserEntry 1 }

ogSerialUserStartTime OBJECT-TYPE
	SYNTAX DateAndTime
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The time and date the user session started."
	::= { ogSerialUserEntry 2 }

ogSerialUserPort OBJECT-TYPE
	SYNTAX Integer32
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"Serial port number"
	::= { ogSerialUserEntry 3 }

ogSerialUserLabel OBJECT-TYPE
	SYNTAX DisplayString (SIZE (0..64))
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The readable label for the serial port."
	::= { ogSerialUserEntry 4 }

ogSerialUserName OBJECT-TYPE
	SYNTAX DisplayString (SIZE (0..64))
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The name of the user logged in on the port."
	::= { ogSerialUserEntry 5 }

ogHostTable OBJECT-TYPE
	SYNTAX  SEQUENCE OF HostEntry
	MAX-ACCESS not-accessible
	STATUS     current
	DESCRIPTION
           "A table of monitored network hosts."
	::= { ogStatus2 4 }

ogHostEntry OBJECT-TYPE
	SYNTAX HostEntry
	MAX-ACCESS not-accessible
	STATUS current
	DESCRIPTION
		"A monitored network host."
	INDEX { ogHostIndex }
	::= { ogHostTable 1 }

HostEntry ::= SEQUENCE {
        ogHostIndex        Integer32,
        ogHostName         DisplayString,
        ogHostIpV4Address  DisplayString,
        ogHostIpV6Address  DisplayString
}

ogHostIndex OBJECT-TYPE
	SYNTAX Integer32 (0..65535)
	MAX-ACCESS not-accessible
	STATUS current
	DESCRIPTION
		"Index within the network host active users table"
	::= { ogHostEntry 1 }

ogHostName OBJECT-TYPE
	SYNTAX DisplayString
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The name of this monitored network host."
	::= { ogHostEntry 2 }

ogHostIpV4Address OBJECT-TYPE
	SYNTAX DisplayString
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The IPv4 Address of this monitored network host."
	::= { ogHostEntry 3 }

ogHostIpV6Address OBJECT-TYPE
	SYNTAX DisplayString
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The IPv6 Address of this monitored network host."
	::= { ogHostEntry 4 }

ogHostServiceTable OBJECT-TYPE
	SYNTAX SEQUENCE OF HostServiceEntry
	MAX-ACCESS not-accessible
	STATUS     current
	DESCRIPTION
           "A table of services belonging to a monitored host."
	::= { ogStatus2 5 }

ogHostServiceEntry OBJECT-TYPE
	SYNTAX HostServiceEntry
	MAX-ACCESS not-accessible
	STATUS current
	DESCRIPTION
		"A monitored host service."
	INDEX { ogHostIndex,
		ogHostServiceIndex }
	::= { ogHostServiceTable 1 }

HostServiceEntry ::= SEQUENCE {
        ogHostServiceIndex       Integer32,
        ogHostServiceHost        OBJECT IDENTIFIER,
        ogHostServiceType        INTEGER,
        ogHostServicePort        Unsigned32,
        ogHostServiceStatus      INTEGER,
        ogHostServiceCounter     Counter32
}

ogHostServiceIndex OBJECT-TYPE
	SYNTAX Integer32 (0..65535)
	MAX-ACCESS not-accessible
	STATUS current
	DESCRIPTION
		"Index within the RPC outlet table"
	::= { ogHostServiceEntry 1 }

ogHostServiceHost OBJECT-TYPE
	SYNTAX OBJECT IDENTIFIER
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The monitored host this service belongs to"
	::= { ogHostServiceEntry 2 }

ogHostServiceType OBJECT-TYPE
	SYNTAX INTEGER {
		tcp(1),
		udp(2)
	}
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The type of service this is."
	::= { ogHostServiceEntry 3 }

ogHostServicePort OBJECT-TYPE
	SYNTAX Unsigned32 (0..65535)
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The TCP Port this service is on."
	::= { ogHostServiceEntry 4 }

ogHostServiceStatus OBJECT-TYPE
	SYNTAX INTEGER {
		unknown(1),
		available(2),
		unavailable(3)
	}
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The availabalilty of this service."
	::= { ogHostServiceEntry 5 }

ogHostServiceCounter OBJECT-TYPE
	SYNTAX Counter32
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The number of alerts related to this service."
	::= { ogHostServiceEntry 6 }

ogHostUserTable OBJECT-TYPE
	SYNTAX  SEQUENCE OF HostUserEntry
	MAX-ACCESS not-accessible
	STATUS     current
	DESCRIPTION
           "This entity's serial port users table."
	::= { ogStatus2 6 }

ogHostUserEntry OBJECT-TYPE
	SYNTAX HostUserEntry
	MAX-ACCESS not-accessible
	STATUS current
	DESCRIPTION
		"A user logged in on the serial port"
	INDEX { ogHostUserIndex }
	::= { ogHostUserTable 1 }

HostUserEntry ::= SEQUENCE {
        ogHostUserIndex        Integer32,
        ogHostUserHost         OBJECT IDENTIFIER,
        ogHostUserStartTime    DateAndTime,
        ogHostUserAddress      DisplayString,
        ogHostUserHostName     DisplayString,
        ogHostUserName         DisplayString
}

ogHostUserIndex OBJECT-TYPE
	SYNTAX Integer32 (0..65535)
	MAX-ACCESS not-accessible
	STATUS current
	DESCRIPTION
		"Index within the network host active users table"
	::= { ogHostUserEntry 1 }

ogHostUserHost OBJECT-TYPE
	SYNTAX OBJECT IDENTIFIER
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The monitored host this user is associated with."
	::= { ogHostUserEntry 2 }

ogHostUserStartTime OBJECT-TYPE
	SYNTAX DateAndTime
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The date and time the user session started."
	::= { ogHostUserEntry 3 }

ogHostUserAddress OBJECT-TYPE
	SYNTAX DisplayString (SIZE (0..64))
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The network host address."
	::= { ogHostUserEntry 4 }

ogHostUserHostName OBJECT-TYPE
	SYNTAX DisplayString (SIZE (0..64))
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The network host's host name."
	::= { ogHostUserEntry 5 }

ogHostUserName OBJECT-TYPE
	SYNTAX DisplayString (SIZE (0..128))
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The network host's active username."
	::= { ogHostUserEntry 6 }

ogWebUserTable OBJECT-TYPE
	SYNTAX  SEQUENCE OF WebUserEntry
	MAX-ACCESS not-accessible
	STATUS     current
	DESCRIPTION
           "This entity's Web Interface users table."
	::= { ogStatus2 7 }

ogWebUserEntry OBJECT-TYPE
	SYNTAX WebUserEntry
	MAX-ACCESS not-accessible
	STATUS current
	DESCRIPTION
		"A user logged in to the Web Interface"
	INDEX { ogWebUserIndex }
	::= { ogWebUserTable 1 }

WebUserEntry ::= SEQUENCE {
        ogWebUserIndex         Integer32,
        ogWebUserStartTime     DateAndTime,
        ogWebUserName          DisplayString,
        ogWebUserSourceAddress DisplayString,
        ogWebUserSourcePort    Integer32
}

ogWebUserIndex OBJECT-TYPE
	SYNTAX Integer32 (0..65535)
	MAX-ACCESS not-accessible
	STATUS current
	DESCRIPTION
		"Index within the Web Interface users table"
	::= { ogWebUserEntry 1 }

ogWebUserStartTime OBJECT-TYPE
	SYNTAX DateAndTime
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The web users session start date and time."
	::= { ogWebUserEntry 2 }

ogWebUserName OBJECT-TYPE
	SYNTAX DisplayString (SIZE (0..64))
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The web users active username."
	::= { ogWebUserEntry 3 }

ogWebUserSourceAddress OBJECT-TYPE
	SYNTAX DisplayString (SIZE (0..64))
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The web users source address."
	::= { ogWebUserEntry 4 }

ogWebUserSourcePort OBJECT-TYPE
	SYNTAX Integer32 (0..65535)
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The web users source tcp port."
	::= { ogWebUserEntry 5 }

ogEmdTable OBJECT-TYPE
	SYNTAX  SEQUENCE OF EmdEntry
	MAX-ACCESS not-accessible
	STATUS     current
	DESCRIPTION
           "This devices temperature monitoring table."
	::= { ogStatus2 8 }

ogEmdEntry OBJECT-TYPE
	SYNTAX EmdEntry
	MAX-ACCESS not-accessible
	STATUS current
	DESCRIPTION
		"EMD status entry"
	INDEX { ogEmdIndex }
	::= { ogEmdTable 1 }

EmdEntry ::= SEQUENCE {
        ogEmdIndex             Integer32,
        ogEmdName              DisplayString,
        ogEmdDescription       DisplayString,
        ogEmdEnabled           INTEGER,
        ogEmdLogEnabled        INTEGER,
        ogEmdConnectType       INTEGER,
        ogEmdTemperatureTotal  Counter32,
        ogEmdHumidityTotal     Counter32,
        ogEmdDioInputTotal     Counter32
}

ogEmdIndex OBJECT-TYPE
	SYNTAX Integer32 (0..65535)
	MAX-ACCESS not-accessible
	STATUS current
	DESCRIPTION
		"Index within the EMD status table"
	::= { ogEmdEntry 1 }

ogEmdName OBJECT-TYPE
	SYNTAX DisplayString (SIZE (0..255))
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The name of the EMD device."
	::= { ogEmdEntry 2 }

ogEmdDescription OBJECT-TYPE
	SYNTAX DisplayString (SIZE (0..255))
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"A description of the EMD device."
	::= { ogEmdEntry 3 }

ogEmdEnabled OBJECT-TYPE
	SYNTAX INTEGER {
		on(1),
		off(2)
	}
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The enabled status of the EMD"
	::= { ogEmdEntry 4 }

ogEmdLogEnabled OBJECT-TYPE
	SYNTAX INTEGER {
		on(1),
		off(2)
	}
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The logging status of the EMD"
	::= { ogEmdEntry 5 }

ogEmdConnectType OBJECT-TYPE
	SYNTAX INTEGER {
		internal(1),
		serial(2),
		network(3)
	}
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"How the EMD device is connected."
	::= { ogEmdEntry 6 }

ogEmdTemperatureTotal OBJECT-TYPE
	SYNTAX Counter32
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The number of temperature sensors contained in this EMD."
	::= { ogEmdEntry 7 }

ogEmdHumidityTotal OBJECT-TYPE
	SYNTAX Counter32
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The number of humidity sensors contained in this EMD."
	::= { ogEmdEntry 8 }

ogEmdDioInputTotal OBJECT-TYPE
	SYNTAX Counter32
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The number of DIOs contained in this EMD."
	::= { ogEmdEntry 9 }

ogEmdTemperatureTable OBJECT-TYPE
	SYNTAX  SEQUENCE OF EmdTemperatureEntry
	MAX-ACCESS not-accessible
	STATUS     current
	DESCRIPTION
           "A table of temperature sensors belonging to EMDs"
	::= { ogStatus2 9 }

ogEmdTemperatureEntry OBJECT-TYPE
	SYNTAX EmdTemperatureEntry
	MAX-ACCESS not-accessible
	STATUS current
	DESCRIPTION
		"EMD status entry"
	INDEX { ogEmdIndex, 
		ogEmdTemperatureIndex }
	::= { ogEmdTemperatureTable 1 }

EmdTemperatureEntry ::= SEQUENCE {
        ogEmdTemperatureIndex        Integer32,
        ogEmdTemperatureEmd          OBJECT IDENTIFIER,
        ogEmdTemperatureName         DisplayString,
        ogEmdTemperatureDescription  DisplayString,
        ogEmdTemperatureValue        Integer32,
        ogEmdTemperatureCounter      Counter32
}

ogEmdTemperatureIndex OBJECT-TYPE
	SYNTAX Integer32 (0..65535)
	MAX-ACCESS not-accessible
	STATUS current
	DESCRIPTION
		"Index within the EMD status table"
	::= { ogEmdTemperatureEntry 1 }

ogEmdTemperatureEmd OBJECT-TYPE
	SYNTAX OBJECT IDENTIFIER
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The EMD this temperature sensor is related to."
	::= { ogEmdTemperatureEntry 2 }

ogEmdTemperatureName OBJECT-TYPE
	SYNTAX DisplayString (SIZE (0..255))
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The name of the EMD temperature sensor."
	::= { ogEmdTemperatureEntry 3 }

ogEmdTemperatureDescription OBJECT-TYPE
	SYNTAX DisplayString (SIZE (0..255))
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"A description of the EMD device."
	::= { ogEmdTemperatureEntry 4 }

ogEmdTemperatureValue OBJECT-TYPE
	SYNTAX Integer32
	UNITS "degrees"
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The current temperature reading on the EMD."
	::= { ogEmdTemperatureEntry 5 }

ogEmdTemperatureCounter OBJECT-TYPE
	SYNTAX Counter32
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"Number of alerts triggered on the EMD."
	::= { ogEmdTemperatureEntry 6 }

ogEmdHumidityTable OBJECT-TYPE
	SYNTAX  SEQUENCE OF EmdHumidityEntry
	MAX-ACCESS not-accessible
	STATUS     current
	DESCRIPTION
           "A table of humidity sensors belonging to EMDs."
	::= { ogStatus2 10 }

ogEmdHumidityEntry OBJECT-TYPE
	SYNTAX EmdHumidityEntry
	MAX-ACCESS not-accessible
	STATUS current
	DESCRIPTION
		"EMD Humidity sensor status entry."
	INDEX { ogEmdIndex,
		ogEmdHumidityIndex }
	::= { ogEmdHumidityTable 1 }

EmdHumidityEntry ::= SEQUENCE {
        ogEmdHumidityIndex        Integer32,
        ogEmdHumidityEmd          OBJECT IDENTIFIER,
        ogEmdHumidityName         DisplayString,
        ogEmdHumidityDescription  DisplayString,
        ogEmdHumidityValue        Integer32,
        ogEmdHumidityCounter      Counter32
}

ogEmdHumidityIndex OBJECT-TYPE
	SYNTAX Integer32 (0..65535)
	MAX-ACCESS not-accessible
	STATUS current
	DESCRIPTION
		"Index within the EMD status table"
	::= { ogEmdHumidityEntry 1 }

ogEmdHumidityEmd OBJECT-TYPE
	SYNTAX OBJECT IDENTIFIER
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The EMD this humidity sensor is related to."
	::= { ogEmdHumidityEntry 2 }

ogEmdHumidityName OBJECT-TYPE
	SYNTAX DisplayString (SIZE (0..255))
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The name of the EMD."
	::= { ogEmdHumidityEntry 3 }

ogEmdHumidityDescription OBJECT-TYPE
	SYNTAX DisplayString (SIZE (0..255))
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"A description of the EMD device."
	::= { ogEmdHumidityEntry 4 }

ogEmdHumidityValue OBJECT-TYPE
	SYNTAX Integer32
	UNITS "percent"
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The current humidity value on the EMD"
	::= { ogEmdHumidityEntry 5 }

ogEmdHumidityCounter OBJECT-TYPE
	SYNTAX Counter32
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"Number of alerts triggered on the EMD"
	::= { ogEmdHumidityEntry 6 }

ogEmdDioTable OBJECT-TYPE
	SYNTAX SEQUENCE OF EmdDioEntry
	MAX-ACCESS not-accessible
	STATUS     current
	DESCRIPTION
           "Ths Digital I/O status table."
	::= { ogStatus2 11 }

ogEmdDioEntry OBJECT-TYPE
	SYNTAX EmdDioEntry
	MAX-ACCESS not-accessible
	STATUS current
	DESCRIPTION
		"Digital I/O status entry"
	INDEX { ogEmdIndex, 
		ogEmdDioIndex }
	::= { ogEmdDioTable 1 }

EmdDioEntry ::= SEQUENCE {
        ogEmdDioIndex        Integer32,
        ogEmdDioEmd          OBJECT IDENTIFIER,
        ogEmdDioName         DisplayString,
        ogEmdDioDescription  DisplayString, 
        ogEmdDioType         INTEGER,
        ogEmdDioDirection    INTEGER,
        ogEmdDioState        INTEGER,
        ogEmdDioTriggerMode  INTEGER,
        ogEmdDioCounter      Counter32
}

ogEmdDioIndex OBJECT-TYPE
	SYNTAX Integer32 (0..65535)
	MAX-ACCESS not-accessible
	STATUS current
	DESCRIPTION
		"Index within the Digital I/O status table"
	::= { ogEmdDioEntry 1 }

ogEmdDioEmd OBJECT-TYPE
	SYNTAX OBJECT IDENTIFIER
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The EMD this Digital I/O relates to."
	::= { ogEmdDioEntry 2 }

ogEmdDioName OBJECT-TYPE
	SYNTAX DisplayString (SIZE (0..255))
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The ID of this Digital I/O."
	::= { ogEmdDioEntry 3 }

ogEmdDioDescription OBJECT-TYPE
	SYNTAX DisplayString (SIZE (0..255))
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"A description of this Digital I/O."
	::= { ogEmdDioEntry 4 }

ogEmdDioType OBJECT-TYPE
	SYNTAX INTEGER {
		ttlInputOutput(1),
		highVoltageOutput(2)
	}
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"Digital I/O type (TTL Input/Output or High-Voltage Output)."
	::= { ogEmdDioEntry 5 }

ogEmdDioDirection OBJECT-TYPE
	SYNTAX INTEGER {
		output(1),
		input(2)
	}
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The direction of the Digital I/O (Input or Output)"
	::= { ogEmdDioEntry 6 }

ogEmdDioState OBJECT-TYPE
	SYNTAX INTEGER {
		high(1),
		low(2),
		unavailable(3)
	}
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The electrical state value of the Digital I/O (Low or High)"
	::= { ogEmdDioEntry 7 }

ogEmdDioTriggerMode OBJECT-TYPE
	SYNTAX INTEGER {
		invalid(1),
		risingEdge(2),
		fallingEdge(3),
		risingFallingEdge(4)
	}
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The Trigger Mode of the Digital I/O"
	::= { ogEmdDioEntry 8 }

ogEmdDioCounter OBJECT-TYPE
	SYNTAX Counter32
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The trigger counter of this Digital I/O"
	::= { ogEmdDioEntry 9 }

ogNetInterfaceTable OBJECT-TYPE
	SYNTAX  SEQUENCE OF NetInterfaceEntry
	MAX-ACCESS not-accessible
	STATUS     current
	DESCRIPTION
           "This devices network interface status table."
	::= { ogStatus2 12 }

ogNetInterfaceEntry OBJECT-TYPE
	SYNTAX NetInterfaceEntry
	MAX-ACCESS not-accessible
	STATUS current
	DESCRIPTION
		"EMD status entry"
	INDEX { ogNetInterfaceIndex }
	::= { ogNetInterfaceTable 1 }

NetInterfaceEntry ::= SEQUENCE {
        ogNetInterfaceIndex Integer32,
        ogNetInterfaceName  DisplayString,
        ogNetInterfaceType  INTEGER,
        ogNetInterfaceState INTEGER
}

ogNetInterfaceIndex OBJECT-TYPE
	SYNTAX Integer32 (0..65535)
	MAX-ACCESS not-accessible
	STATUS current
	DESCRIPTION
		"Index within the network interface status table"
	::= { ogNetInterfaceEntry 1 }

ogNetInterfaceName OBJECT-TYPE
	SYNTAX DisplayString (SIZE (0..255))
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The name of a network interface."
	::= { ogNetInterfaceEntry 2 }

ogNetInterfaceType OBJECT-TYPE
	SYNTAX INTEGER {
		unavailable(1),
		ethernet(2),
		wifi(3),
		cellModem(4),
		v92Modem(5),
		vpn(6)
	}
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The type of this network interface entry."
	::= { ogNetInterfaceEntry 3 }

ogNetInterfaceState OBJECT-TYPE
	SYNTAX INTEGER {
		unavailable(1),
		down(2),
		starting(3),
		up(4),
		stopping(5)
	}
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The current status of this network interface entry."
	::= { ogNetInterfaceEntry 4 }

ogPowerSupplyTable OBJECT-TYPE
	SYNTAX  SEQUENCE OF PowerSupplyEntry
	MAX-ACCESS not-accessible
	STATUS     current
	DESCRIPTION
           "This entity's Power Supply table."
	::= { ogStatus2 13 }

ogPowerSupplyEntry OBJECT-TYPE
	SYNTAX PowerSupplyEntry
	MAX-ACCESS not-accessible
	STATUS current
	DESCRIPTION
		"Power Supply status entry"
	INDEX { ogPowerSupplyIndex }
	::= { ogPowerSupplyTable 1 }

PowerSupplyEntry ::= SEQUENCE {
        ogPowerSupplyIndex          Integer32,
        ogPowerSupplyName           DisplayString,
        ogPowerSupplyInputVoltage   Integer32,
        ogPowerSupplyOutputCurrent  Integer32,
        ogPowerSupplyTemperature    Integer32
}

ogPowerSupplyIndex OBJECT-TYPE
	SYNTAX Integer32 (1..65535)
	MAX-ACCESS not-accessible
	STATUS current
	DESCRIPTION
		"Index within the Power Supply status table"
	::= { ogPowerSupplyEntry 1 }

ogPowerSupplyName OBJECT-TYPE
	SYNTAX DisplayString (SIZE (0..255))
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The name of the Power Supply."
	::= { ogPowerSupplyEntry 2 }

ogPowerSupplyInputVoltage OBJECT-TYPE
	SYNTAX Integer32
	UNITS "volts"
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"Input voltage of the Power Supply"
	::= { ogPowerSupplyEntry 3 }

ogPowerSupplyOutputCurrent OBJECT-TYPE
	SYNTAX Integer32
	UNITS "0.01 Amps"
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"Output current of the Power Supply"
	::= { ogPowerSupplyEntry 4 }

ogPowerSupplyTemperature OBJECT-TYPE
	SYNTAX Integer32
	UNITS "degrees celsius"
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"Temperature of the Power Supply"
	::= { ogPowerSupplyEntry 5 }

ogUpsTable OBJECT-TYPE
	SYNTAX  SEQUENCE OF UpsEntry
	MAX-ACCESS not-accessible
	STATUS     current
	DESCRIPTION
           "Ths Uninterruptable Power Supply (UPS) status table."
	::= { ogStatus2 14 }

ogUpsEntry OBJECT-TYPE
	SYNTAX UpsEntry
	MAX-ACCESS not-accessible
	STATUS current
	DESCRIPTION
		"Digital I/O status entry"
	INDEX { ogUpsIndex }
	::= { ogUpsTable 1 }

UpsEntry ::= SEQUENCE {
        ogUpsIndex                   Integer32,
        ogUpsName                    DisplayString,
        ogUpsDescription             DisplayString,
        ogUpsType                    DisplayString,
        ogUpsLogEnabled              INTEGER,
        ogUpsConnectType             INTEGER,
        ogUpsState                   INTEGER,
        ogUpsTemperature             Integer32,
        ogUpsHumidity                Integer32,
        ogUpsBatteryState            INTEGER,
        ogUpsBatteryRunTime          Integer32,
        ogUpsBatteryRunTimeLow       Integer32,
        ogUpsBatteryRunTimeRestart   Integer32,
        ogUpsBatteryCharge           Integer32,
        ogUpsBatteryVoltage          Integer32,
        ogUpsBatteryNominalVoltage   Integer32,
        ogUpsBatteryCurrent          Integer32,
        ogUpsBatteryNominalCurrent   Integer32,
        ogUpsBatteryTemperature      Integer32,
        ogUpsInputFrequency          Integer32,
        ogUpsInputNominalFrequency   Integer32,
        ogUpsInputVoltage            Integer32,
        ogUpsInputNominalVoltage     Integer32,
        ogUpsInputCurrent            Integer32,
        ogUpsInputNominalCurrent     Integer32,
        ogUpsOutputFrequency         Integer32,
        ogUpsOutputNominalFrequency  Integer32,
        ogUpsOutputVoltage           Integer32,
        ogUpsOutputNominalVoltage    Integer32,
        ogUpsOutputCurrent           Integer32,
        ogUpsOutputNominalCurrent    Integer32,
        ogUpsOutputLoad              Integer32,
        ogUpsOutputPower             Integer32,
        ogUpsOutputTruePower         Integer32,
        ogUpsCounter                 Counter32
}

ogUpsIndex OBJECT-TYPE
	SYNTAX Integer32 (0..65535)
	MAX-ACCESS not-accessible
	STATUS current
	DESCRIPTION
		"Index within the UPS status table."
	::= { ogUpsEntry 1 }

ogUpsName OBJECT-TYPE
	SYNTAX DisplayString (SIZE (0..255))
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The ID of this UPS."
	::= { ogUpsEntry 2 }

ogUpsDescription OBJECT-TYPE
	SYNTAX DisplayString (SIZE (0..255))
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"A description of this UPS."
	::= { ogUpsEntry 3 }

ogUpsType OBJECT-TYPE
	SYNTAX DisplayString (SIZE (0..255))
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The UPS driver type."
	::= { ogUpsEntry 4 }

ogUpsLogEnabled OBJECT-TYPE
	SYNTAX INTEGER {
		on(1),
		off(2)
	}
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The logging status of the UPS"
	::= { ogUpsEntry 5 }

ogUpsConnectType OBJECT-TYPE
	SYNTAX INTEGER {
		unknown(1),
		usb(2),
		http(3),
		https(4),
		snmp(5),
		serial(6)
	}
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"How the UPS device is being monitored."
	::= { ogUpsEntry 6 }

ogUpsState OBJECT-TYPE
	SYNTAX INTEGER {
		unknown(1),
		onLine(2),
		onBattery(3),
		lowBattery(4),
		onBypass(5)
	}
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The current state the UPS is running in."
	::= { ogUpsEntry 7 }

ogUpsTemperature OBJECT-TYPE
	SYNTAX Integer32
	UNITS "degrees"
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The UPS temperature. Negative if unavailable."
	::= { ogUpsEntry 8 }

ogUpsHumidity OBJECT-TYPE
	SYNTAX Integer32
	UNITS "percent"
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The UPS humidity. Negative if unavailable."
	::= { ogUpsEntry 9 }

ogUpsBatteryState OBJECT-TYPE
	SYNTAX INTEGER {
		unknown(1),
		normal(2),
		warning(3),
		low(4),
		depleted(5)
	}
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The current state of the UPS battery."
	::= { ogUpsEntry 10 }

ogUpsBatteryRunTime OBJECT-TYPE
	SYNTAX Integer32 (-1..31449600)
	UNITS "seconds"
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"Battery runtime (seconds). Negative if unavailable"
	::= { ogUpsEntry 11 }

ogUpsBatteryRunTimeLow OBJECT-TYPE
	SYNTAX Integer32 (-1..31449600)
	UNITS "seconds"
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"Estimated remaining battery runtime when UPS switches to Low
		Battery. Negative if unavailable."
	::= { ogUpsEntry 12 }

ogUpsBatteryRunTimeRestart OBJECT-TYPE
	SYNTAX Integer32 (-1..31449600)
	UNITS "seconds"
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"Minimum battery runtime for UPS restart after power-off
		(seconds). Negative if unavailable."
	::= { ogUpsEntry 13 }

ogUpsBatteryCharge OBJECT-TYPE
	SYNTAX Integer32 (-1..100)
	UNITS "percent"
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"Estimated percent of Battery charge remaining. Negative if
		unavailable."
	::= { ogUpsEntry 14 }

ogUpsBatteryVoltage OBJECT-TYPE
	SYNTAX Integer32
	UNITS "0.1 Volt DC"
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The magnitude of the current battery voltage. Negative if
		unavailable."
	::= { ogUpsEntry 15 }

ogUpsBatteryNominalVoltage OBJECT-TYPE
	SYNTAX Integer32
	UNITS "0.1 Volt DC"
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"Nominal battery voltage (V). Negative if unavailable."
	::= { ogUpsEntry 16 }

ogUpsBatteryCurrent OBJECT-TYPE
	SYNTAX Integer32
	UNITS "0.1 Amp DC"
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The UPS battery current. Negative if unavailable."
	::= { ogUpsEntry 17 }

ogUpsBatteryNominalCurrent OBJECT-TYPE
	SYNTAX Integer32
	UNITS "0.1 Amp DC"
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The nominal UPS battery current. Negative if unavailable."
	::= { ogUpsEntry 18 }

ogUpsBatteryTemperature OBJECT-TYPE
	SYNTAX Integer32
	UNITS "degrees"
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The UPS battery temperature. Negative if unavailable."
	::= { ogUpsEntry 19 }

ogUpsInputFrequency OBJECT-TYPE
	SYNTAX Integer32
	UNITS "Hz"
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"Input line frequency (Hz). Negative if unavailable."
	::= { ogUpsEntry 20 }

ogUpsInputNominalFrequency OBJECT-TYPE
	SYNTAX Integer32
	UNITS "Hz"
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"Nominal input line frequency (Hz). Negative if unavailable."
	::= { ogUpsEntry 21 }

ogUpsInputVoltage OBJECT-TYPE
	SYNTAX Integer32
	UNITS "RMS Volts"
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The magnitude of the UPS input voltage. Negative if
		unavailable."
	::= { ogUpsEntry 22 }

ogUpsInputNominalVoltage OBJECT-TYPE
	SYNTAX Integer32
	UNITS "RMS Volts"
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The nominal input voltage. Negative if unavailable."
	::= { ogUpsEntry 23 }

ogUpsInputCurrent OBJECT-TYPE
	SYNTAX Integer32
	UNITS "0.1 RMS Amp"
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The input current. Negative if unavailable."
	::= { ogUpsEntry 24 }

ogUpsInputNominalCurrent OBJECT-TYPE
	SYNTAX Integer32
	UNITS "0.1 RMS Amp"
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The nominal input current. Negative if unavailable."
	::= { ogUpsEntry 25 }

ogUpsOutputFrequency OBJECT-TYPE
	SYNTAX Integer32
	UNITS "Hz"
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"Output line frequency (Hz). Negative if unavailable."
	::= { ogUpsEntry 26 }

ogUpsOutputNominalFrequency OBJECT-TYPE
	SYNTAX Integer32
	UNITS "Hz"
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"Nominal output line frequency (Hz). Negative if unavailable."
	::= { ogUpsEntry 27 }

ogUpsOutputVoltage OBJECT-TYPE
	SYNTAX Integer32
	UNITS "RMS Volts"
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The magnitude of the UPS output voltage. Negative if 
		unavailable."
	::= { ogUpsEntry 28 }

ogUpsOutputNominalVoltage OBJECT-TYPE
	SYNTAX Integer32
	UNITS "RMS Volts"
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The nominal magnitude of the UPS output voltage. Negative if 
		unavailable."
	::= { ogUpsEntry 29 }

ogUpsOutputCurrent OBJECT-TYPE
	SYNTAX Integer32
	UNITS "0.1 RMS Amp"
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The magnitude of the UPS input current. Negative if
		unavailable."
	::= { ogUpsEntry 30 }

ogUpsOutputNominalCurrent OBJECT-TYPE
	SYNTAX Integer32
	UNITS "0.1 RMS Amp"
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The nominal magnitude of the UPS input current. Negative if
		unavailable."
	::= { ogUpsEntry 31 }

ogUpsOutputLoad OBJECT-TYPE
	SYNTAX Integer32 (0..100)
	UNITS "percent"
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"Estimated percent of UPS power capacity being used."
	::= { ogUpsEntry 32 }

ogUpsOutputPower OBJECT-TYPE
	SYNTAX Integer32
	UNITS "Volt-Amps"
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The current value of apparent power (Volt-Amps).
		Negative if unavailable."
	::= { ogUpsEntry 33 }

ogUpsOutputTruePower OBJECT-TYPE
	SYNTAX Integer32
	UNITS "Watts"
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The current value of real power (Watts).
		Negative if unavailable."
	::= { ogUpsEntry 34 }

ogUpsCounter OBJECT-TYPE
	SYNTAX Counter32
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"Number of alerts triggered on the UPS"
	::= { ogUpsEntry 35 }

ogRpcTable OBJECT-TYPE
	SYNTAX  SEQUENCE OF RpcEntry
	MAX-ACCESS not-accessible
	STATUS     current
	DESCRIPTION
           "This entity's Remote Power Controller (RPC) table."
	::= { ogStatus2 15 }

ogRpcEntry OBJECT-TYPE
	SYNTAX RpcEntry
	MAX-ACCESS not-accessible
	STATUS current
	DESCRIPTION
		"RPC status entry"
	INDEX { ogRpcIndex }
	::= { ogRpcTable 1 }

RpcEntry ::= SEQUENCE {
        ogRpcIndex          Integer32,
        ogRpcName           DisplayString,
        ogRpcDescription    DisplayString,
        ogRpcType           DisplayString,
        ogRpcLogEnabled     INTEGER,
        ogRpcOutletTotal    Counter32,
        ogRpcMaxTemperature Integer32,
        ogRpcConnectType    INTEGER,
        ogRpcInputFrequency Integer32,
        ogRpcInputVoltage   Integer32,
        ogRpcInputCurrent   Integer32,
        ogRpcCounter        Counter32
}

ogRpcIndex OBJECT-TYPE
	SYNTAX Integer32 (1..65535)
	MAX-ACCESS not-accessible
	STATUS current
	DESCRIPTION
		"Index within the RPC status table"
	::= { ogRpcEntry 1 }

ogRpcName OBJECT-TYPE
	SYNTAX DisplayString (SIZE (0..255))
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The name of the RPC device."
	::= { ogRpcEntry 2 }

ogRpcDescription OBJECT-TYPE
	SYNTAX DisplayString (SIZE (0..255))
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"A description for the RPC device."
	::= { ogRpcEntry 3 }

ogRpcType OBJECT-TYPE
	SYNTAX DisplayString (SIZE (0..255))
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"A type for the RPC device."
	::= { ogRpcEntry 4 }

ogRpcLogEnabled OBJECT-TYPE
	SYNTAX INTEGER {
		on(1),
		off(2)
	}
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The logging status of the RPC"
	::= { ogRpcEntry 5 }

ogRpcOutletTotal OBJECT-TYPE
	SYNTAX Counter32
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The number of outlets on this RPC"
	::= { ogRpcEntry 6 }

ogRpcMaxTemperature OBJECT-TYPE
	SYNTAX Integer32
	UNITS "degrees"
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"Maximum temperature on the RPC"
	::= { ogRpcEntry 7 }

ogRpcConnectType OBJECT-TYPE
	SYNTAX INTEGER {
		serial(1),
		network(2)
	}
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"How the RPC device is connected."
	::= { ogRpcEntry 8 }

ogRpcInputFrequency OBJECT-TYPE
	SYNTAX Integer32
	UNITS "Hz"
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"Input line frequency (Hz). Negative if unavailable."
	::= { ogRpcEntry 9 }

ogRpcInputVoltage OBJECT-TYPE
	SYNTAX Integer32
	UNITS "RMS Volts"
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The magnitude of the RPC input voltage. Negative if
		unavailable."
	::= { ogRpcEntry 10 }

ogRpcInputCurrent OBJECT-TYPE
	SYNTAX Integer32
	UNITS "0.1 RMS Amp"
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The input current. Negative if unavailable."
	::= { ogRpcEntry 11 }

ogRpcCounter OBJECT-TYPE
	SYNTAX Counter32
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"Number of alerts triggered on the RPC"
	::= { ogRpcEntry 12 }

ogRpcOutletTable OBJECT-TYPE
	SYNTAX SEQUENCE OF RpcOutletEntry
	MAX-ACCESS not-accessible
	STATUS     current
	DESCRIPTION
           "This RPC's outlet table."
	::= { ogStatus2 16 }

ogRpcOutletEntry OBJECT-TYPE
	SYNTAX RpcOutletEntry
	MAX-ACCESS not-accessible
	STATUS current
	DESCRIPTION
		"RPC Outlet status entry"
	INDEX { ogRpcIndex,
		ogRpcOutletIndex }
	::= { ogRpcOutletTable 1 }

RpcOutletEntry ::= SEQUENCE {
        ogRpcOutletIndex       Integer32,
        ogRpcOutletRpc         OBJECT IDENTIFIER,
        ogRpcOutletName        DisplayString,
        ogRpcOutletState       INTEGER,
        ogRpcOutletFrequency   Integer32,
        ogRpcOutletVoltage     Integer32,
        ogRpcOutletCurrent     Integer32,
        ogRpcOutletLoad        Integer32
}

ogRpcOutletIndex OBJECT-TYPE
	SYNTAX Integer32 (0..65535)
	MAX-ACCESS not-accessible
	STATUS current
	DESCRIPTION
		"Index within the RPC outlet table"
	::= { ogRpcOutletEntry 1 }

ogRpcOutletRpc OBJECT-TYPE
	SYNTAX OBJECT IDENTIFIER
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The RPC this outlet belongs to"
	::= { ogRpcOutletEntry 2 }

ogRpcOutletName OBJECT-TYPE
	SYNTAX DisplayString (SIZE (0..255))
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The name of the RPC outlet."
	::= { ogRpcOutletEntry 3 }

ogRpcOutletState OBJECT-TYPE
	SYNTAX INTEGER {
		on(1),
		off(2),
		transitioning(3),
		unavailable(4)
	}
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The power status of the RPC outlet"
	::= { ogRpcOutletEntry 4 }

ogRpcOutletFrequency OBJECT-TYPE
	SYNTAX Integer32
	UNITS "Hz"
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"Output line frequency (Hz). Negative if unavailable."
	::= { ogRpcOutletEntry 5 }

ogRpcOutletVoltage OBJECT-TYPE
	SYNTAX Integer32 (-1..2640)
        UNITS "0.01 Amps"
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The voltage on this outlet. Negative if unavailable."
	::= { ogRpcOutletEntry 6 }

ogRpcOutletCurrent OBJECT-TYPE
	SYNTAX Integer32 (-1..25500)
        UNITS "0.01 Amps"
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"Current measured on this outlet. Negative if unavailable."
	::= { ogRpcOutletEntry 7 }

ogRpcOutletLoad OBJECT-TYPE
	SYNTAX Integer32 (-1..100)
	UNITS "percent"
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"Estimated percent of RPC outlet power capacity being used."
	::= { ogRpcOutletEntry 8 }

ogCellModemTable OBJECT-TYPE
	SYNTAX  SEQUENCE OF CellModemEntry
	MAX-ACCESS not-accessible
	STATUS     current
	DESCRIPTION
           "Ths cellular modem status table."
	::= { ogStatus2 17 }

ogCellModemEntry OBJECT-TYPE
	SYNTAX CellModemEntry
	MAX-ACCESS not-accessible
	STATUS current
	DESCRIPTION
		"A cellular modem status entry."
	INDEX { ogCellModemIndex }
	::= { ogCellModemTable 1 }

CellModemEntry ::= SEQUENCE {
        ogCellModemIndex           Integer32,
        ogCellModemVendor          DisplayString,
        ogCellModemModel           DisplayString,
        ogCellModemEnabled         INTEGER,
        ogCellModemConnected       INTEGER,
        ogCellModemNetwork         DisplayString,
        ogCellModemRegistered      INTEGER,
        ogCellModemTower           Integer32,
        ogCellModemRadioTechnology INTEGER,
        ogCellModemApn             DisplayString,
        ogCellModem3gRssi          Integer32,
        ogCellModem4gRssi          Integer32,
        ogCellModemSessionTime     Counter32,
        ogCellModemSelectedSimCard Counter32,
        ogCellModemTemperature     Integer32,
        ogCellModemCounter         Counter32,
	ogCellModemIMSI            DisplayString
}

ogCellModemIndex OBJECT-TYPE
	SYNTAX Integer32 (0..65535)
	MAX-ACCESS not-accessible
	STATUS current
	DESCRIPTION
		"Index of the cellular modem status entry."
	::= { ogCellModemEntry 1 }

ogCellModemVendor OBJECT-TYPE
	SYNTAX DisplayString (SIZE (0..255))
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The Manufacturer ID of Cellular Modem."
	::= { ogCellModemEntry 2 }

ogCellModemModel OBJECT-TYPE
	SYNTAX DisplayString (SIZE (0..255))
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The Cellular Modem model name."
	::= { ogCellModemEntry 3 }

ogCellModemEnabled OBJECT-TYPE
	SYNTAX INTEGER {
		enabled(1),
		disabled(2)
	}
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The enabled state of the modem."
	::= { ogCellModemEntry 4 }

ogCellModemConnected OBJECT-TYPE
	SYNTAX INTEGER {
		connected(1),
		disconnected(2)
	}
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The connected state of the modem."
	::= { ogCellModemEntry 5 }

ogCellModemNetwork OBJECT-TYPE
	SYNTAX DisplayString (SIZE (0..255))
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The name of the network provider."
	::= { ogCellModemEntry 6 }

ogCellModemRegistered OBJECT-TYPE
	SYNTAX INTEGER {
		registered(1),
		unregistered(2)
	}
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The registration state of the modem."
	::= { ogCellModemEntry 7 }

ogCellModemTower OBJECT-TYPE
	SYNTAX Integer32
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The current cellular tower ID."
	::= { ogCellModemEntry 8 }

ogCellModemRadioTechnology OBJECT-TYPE
	SYNTAX INTEGER {
		unavailable(1),
		cdma(2),
		evdo(3),
		gsm(4),
		umts(5),
		lte(6)
	}
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The current Radio Access Technology being used"
	::= { ogCellModemEntry 9 }

ogCellModemApn OBJECT-TYPE
	SYNTAX DisplayString (SIZE (0..255))
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The APN configured for this cellmodem."
	::= { ogCellModemEntry 10 }

ogCellModem3gRssi OBJECT-TYPE
	SYNTAX Integer32 (-99..99)
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The current 3G Received Signal Strength (RSSI) if applicable."
	::= { ogCellModemEntry 11 }

ogCellModem4gRssi OBJECT-TYPE
	SYNTAX Integer32 (-99..99)
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The current 4G Received Signal Strength (RSSI) if applicable."
	::= { ogCellModemEntry 12 }

ogCellModemSessionTime OBJECT-TYPE
	SYNTAX Counter32
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The number of seconds the modem session has been up for."
	::= { ogCellModemEntry 13 }

ogCellModemSelectedSimCard OBJECT-TYPE
	SYNTAX Counter32
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The SIM card currently being used by this modem."
	::= { ogCellModemEntry 14 }

ogCellModemTemperature OBJECT-TYPE
	SYNTAX Integer32
	UNITS "degrees"
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The current temperature of the Cellular Modem."
	::= { ogCellModemEntry 15 }

ogCellModemCounter OBJECT-TYPE
	SYNTAX Counter32
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The number of alerts the modem has triggered."
	::= { ogCellModemEntry 16 }

ogCellModemIMSI OBJECT-TYPE
	SYNTAX DisplayString (SIZE (0..255))
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The IMSI of the SIM currently in use by the Cellular Modem."
	::= { ogCellModemEntry 17 }

ogWifiClientTable OBJECT-TYPE
	SYNTAX  SEQUENCE OF WifiClientEntry
	MAX-ACCESS not-accessible
	STATUS     current
	DESCRIPTION
           "Ths wireless client status table."
	::= { ogStatus2 18 }

ogWifiClientEntry OBJECT-TYPE
	SYNTAX WifiClientEntry
	MAX-ACCESS not-accessible
	STATUS current
	DESCRIPTION
		"A wireless client status entry."
	INDEX { ogWifiClientIndex }
	::= { ogWifiClientTable 1 }

WifiClientEntry ::= SEQUENCE {
        ogWifiClientIndex            Integer32,
        ogWifiClientInterface        DisplayString,
        ogWifiClientEnabled          INTEGER,
        ogWifiClientEssid            DisplayString,
        ogWifiClientIeeeMode         INTEGER,
        ogWifiClientMode             INTEGER,
        ogWifiClientFrequency        Unsigned32,
        ogWifiClientApMac            DisplayString,
        ogWifiClientBitRate          Unsigned32,
        ogWifiClientTxPower          Integer32,
        ogWifiClientLinkQuality      Unsigned32,
        ogWifiClientRssi             Integer32,
        ogWifiClientRxInvalidNwid    Counter32,
        ogWifiClientRxInvalidCrypt   Counter32,
        ogWifiClientRxInvalidFrag    Counter32,
        ogWifiClientRxInvalidRetries Counter32,
        ogWifiClientRxInvalidMisc    Counter32,
        ogWifiClientMissedBeacon     Counter32,
        ogWifiClientCounter          Counter32
}

ogWifiClientIndex OBJECT-TYPE
	SYNTAX Integer32 (0..65535)
	MAX-ACCESS not-accessible
	STATUS current
	DESCRIPTION
		"Index of the wireless client status entry."
	::= { ogWifiClientEntry 1 }

ogWifiClientInterface OBJECT-TYPE
	SYNTAX DisplayString (SIZE (0..16))
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The wireless client network interface name."
	::= { ogWifiClientEntry 2 }

ogWifiClientEnabled OBJECT-TYPE
	SYNTAX INTEGER {
		on(1),
		off(2)
	}
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The wireless client enabled state"
	::= { ogWifiClientEntry 3 }

ogWifiClientEssid OBJECT-TYPE
	SYNTAX DisplayString (SIZE (0..255))
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The ESSID this wireless client is currently associated with."
	::= { ogWifiClientEntry 4 }

ogWifiClientIeeeMode OBJECT-TYPE
	SYNTAX INTEGER {
		unavailable(1),
		ieee802Dot11B(2),
		ieee802Dot11BG(3),
		ieee802Dot11BGN(4),
		ieee802Dot11ABGN(5)
	}
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The IEEE 802.11 mode of this wireless client."
	::= { ogWifiClientEntry 5 }

ogWifiClientMode OBJECT-TYPE
	SYNTAX INTEGER {
		unavailable(1),
		managed(2),
		adhoc(3)
	}
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The operating mode of this wireless client."
	::= { ogWifiClientEntry 6 }

ogWifiClientFrequency OBJECT-TYPE
	SYNTAX Unsigned32
	UNITS  "0.0001 THz"
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The current frequency of this wireless client."
	::= { ogWifiClientEntry 7 }

ogWifiClientApMac OBJECT-TYPE
	SYNTAX DisplayString (SIZE (0..32))
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The Access Point ID this wireless client is associated with."
	::= { ogWifiClientEntry 8 }

ogWifiClientBitRate OBJECT-TYPE
	SYNTAX Unsigned32
	UNITS  "Mb/s"
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The current bit-rate of this wireless client."
	::= { ogWifiClientEntry 9 }

ogWifiClientTxPower OBJECT-TYPE
	SYNTAX Integer32
	UNITS  "dBm"
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The current Tx-Power of this wireless client."
	::= { ogWifiClientEntry 10 }

ogWifiClientLinkQuality OBJECT-TYPE
	SYNTAX Unsigned32
	UNITS  "percent"
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The normalized link quality of this wireless client."
	::= { ogWifiClientEntry 11 }

ogWifiClientRssi OBJECT-TYPE
	SYNTAX Integer32
	UNITS  "dBm"
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The current Signal Level of this wireless client."
	::= { ogWifiClientEntry 12 }

ogWifiClientRxInvalidNwid OBJECT-TYPE
	SYNTAX Counter32
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The count of invalid Network ID's for this wireless client."
	::= { ogWifiClientEntry 13 }

ogWifiClientRxInvalidCrypt OBJECT-TYPE
	SYNTAX Counter32
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The count of invalid crypt's for this wireless client."
	::= { ogWifiClientEntry 14 }

ogWifiClientRxInvalidFrag OBJECT-TYPE
	SYNTAX Counter32
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The count of invalid frag's for this wireless client."
	::= { ogWifiClientEntry 15 }

ogWifiClientRxInvalidRetries OBJECT-TYPE
	SYNTAX Counter32
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The count of invalid retries for this wireless client."
	::= { ogWifiClientEntry 16 }

ogWifiClientRxInvalidMisc OBJECT-TYPE
	SYNTAX Counter32
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The count of invalid misc's for this wireless client."
	::= { ogWifiClientEntry 17 }

ogWifiClientMissedBeacon OBJECT-TYPE
	SYNTAX Counter32
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The count of missed beacon's for this wireless client."
	::= { ogWifiClientEntry 18 }

ogWifiClientCounter OBJECT-TYPE
	SYNTAX Counter32
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The number of alerts triggered by this wireless client."
	::= { ogWifiClientEntry 19 }

ogWifiApTable OBJECT-TYPE
	SYNTAX  SEQUENCE OF WifiApEntry
	MAX-ACCESS not-accessible
	STATUS     current
	DESCRIPTION
           "Ths wireless interface status table."
	::= { ogStatus2 19 }

ogWifiApEntry OBJECT-TYPE
	SYNTAX WifiApEntry
	MAX-ACCESS not-accessible
	STATUS current
	DESCRIPTION
		"A wireless interface status entry"
	INDEX { ogWifiApIndex }
	::= { ogWifiApTable 1 }

WifiApEntry ::= SEQUENCE {
        ogWifiApIndex     Integer32,
        ogWifiApInterface DisplayString,
        ogWifiApEnabled   INTEGER,
        ogWifiApSsid      DisplayString,
        ogWifiApIeeeMode  INTEGER,
        ogWifiApFrequency Unsigned32,
        ogWifiApTxPower   Integer32,
        ogWifiApCounter   Counter32
}

ogWifiApIndex OBJECT-TYPE
	SYNTAX Integer32 (0..65535)
	MAX-ACCESS not-accessible
	STATUS current
	DESCRIPTION
		"Index of the wireless server status entry."
	::= { ogWifiApEntry 1 }

ogWifiApInterface OBJECT-TYPE
	SYNTAX DisplayString (SIZE (0..16))
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The wireless access point network interface name."
	::= { ogWifiApEntry 2 }

ogWifiApEnabled OBJECT-TYPE
	SYNTAX INTEGER {
		on(1),
		off(2)
	}
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The enabled status of the wireless server."
	::= { ogWifiApEntry 3 }

ogWifiApSsid OBJECT-TYPE
	SYNTAX DisplayString (SIZE (0..255))
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The SSID for this wireless access point."
	::= { ogWifiApEntry 4 }

ogWifiApIeeeMode OBJECT-TYPE
	SYNTAX INTEGER {
		unavailable(1),
		ieee802Dot11B(2),
		ieee802Dot11BG(3),
		ieee802Dot11BGN(4),
		ieee802Dot11ABGN(5)
	}
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The IEEE 802.11 mode of this wireless access point."
	::= { ogWifiApEntry 5 }

ogWifiApFrequency OBJECT-TYPE
	SYNTAX Unsigned32
	UNITS  "0.0001 THz"
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The current frequency of this wireless access point."
	::= { ogWifiApEntry 6 }

ogWifiApTxPower OBJECT-TYPE
	SYNTAX Integer32
	UNITS  "dBm"
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The current Tx-Power of this wireless access point."
	::= { ogWifiApEntry 7 }

ogWifiApCounter OBJECT-TYPE
	SYNTAX Counter32
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The number of alerts triggered by this wireless access point."
	::= { ogWifiApEntry 8 }

ogWifiApClientTable OBJECT-TYPE
	SYNTAX SEQUENCE OF WifiApClientEntry
	MAX-ACCESS not-accessible
	STATUS     current
	DESCRIPTION
           "This RPC's outlet table."
	::= { ogStatus2 20 }

ogWifiApClientEntry OBJECT-TYPE
	SYNTAX WifiApClientEntry
	MAX-ACCESS not-accessible
	STATUS current
	DESCRIPTION
		"RPC Outlet status entry"
	INDEX { ogWifiApIndex,
		ogWifiApClientIndex }
	::= { ogWifiApClientTable 1 }

WifiApClientEntry ::= SEQUENCE {
        ogWifiApClientIndex        Integer32,
        ogWifiApClientAp           OBJECT IDENTIFIER,
        ogWifiApClientMac          DisplayString,
        ogWifiApClientInactiveTime Counter32,
        ogWifiApClientRxBytes      Counter32,
        ogWifiApClientRxPackets    Counter32,
        ogWifiApClientTxBytes      Counter32,
        ogWifiApClientTxPackets    Counter32,
        ogWifiApClientRssi         Integer32,
        ogWifiApClientTxBitRate    Unsigned32
}

ogWifiApClientIndex OBJECT-TYPE
	SYNTAX Integer32 (0..65535)
	MAX-ACCESS not-accessible
	STATUS current
	DESCRIPTION
		"Index within the wireless AP client table"
	::= { ogWifiApClientEntry 1 }

ogWifiApClientAp OBJECT-TYPE
	SYNTAX OBJECT IDENTIFIER
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The wireless AP this client is assiciated with."
	::= { ogWifiApClientEntry 2 }

ogWifiApClientMac OBJECT-TYPE
	SYNTAX DisplayString (SIZE (0..32))
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The MAC address of the Access Point this wireless client is associated with."
	::= { ogWifiApClientEntry 3 }

ogWifiApClientInactiveTime OBJECT-TYPE
	SYNTAX Counter32
	UNITS  "milliseconds"
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The Inactive Time for this wireless client."
	::= { ogWifiApClientEntry 4 }

ogWifiApClientRxBytes OBJECT-TYPE
	SYNTAX Counter32
	UNITS  "bytes"
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The number of received bytes for this wireless client."
	::= { ogWifiApClientEntry 5 }

ogWifiApClientRxPackets OBJECT-TYPE
	SYNTAX Counter32
	UNITS  "packets"
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The number of received packets for this wireless client."
	::= { ogWifiApClientEntry 6 }

ogWifiApClientTxBytes OBJECT-TYPE
	SYNTAX Counter32
	UNITS  "bytes"
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The number of transmitted bytes for this wireless client."
	::= { ogWifiApClientEntry 7 }

ogWifiApClientTxPackets OBJECT-TYPE
	SYNTAX Counter32
	UNITS  "packets"
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The number of transmitted packets for this wireless client."
	::= { ogWifiApClientEntry 8 }

ogWifiApClientRssi OBJECT-TYPE
	SYNTAX Integer32
	UNITS  "dBm"
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The current Signal Level of this wireless client."
	::= { ogWifiApClientEntry 9 }

ogWifiApClientTxBitRate OBJECT-TYPE
	SYNTAX Unsigned32
	UNITS  "Mb/s"
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The current transmission bit-rate of this wireless client."
	::= { ogWifiApClientEntry 10 }

ogCheckTable OBJECT-TYPE
	SYNTAX  SEQUENCE OF CheckEntry
	MAX-ACCESS not-accessible
	STATUS     current
	DESCRIPTION
           "Ths auto-response check table."
	::= { ogStatus2 21 }

ogCheckEntry OBJECT-TYPE
	SYNTAX CheckEntry
	MAX-ACCESS not-accessible
	STATUS current
	DESCRIPTION
		"An auto-response check entry"
	INDEX { ogCheckIndex }
	::= { ogCheckTable 1 }

CheckEntry ::= SEQUENCE {
        ogCheckIndex          Integer32,
        ogCheckName           DisplayString,
        ogCheckRepeatTimeout  Integer32,
        ogCheckResetTimeout   Integer32,
        ogCheckType           INTEGER,
        ogCheckTriggerActions Counter32,
        ogCheckResolveActions Counter32
}

ogCheckIndex OBJECT-TYPE
	SYNTAX Integer32 (0..65535)
	MAX-ACCESS not-accessible
	STATUS current
	DESCRIPTION
		"Index of the auto-response rule"
	::= { ogCheckEntry 1 }

ogCheckName OBJECT-TYPE
	SYNTAX DisplayString (SIZE (0..255))
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The ID of this auto-response rule."
	::= { ogCheckEntry 2 }

ogCheckRepeatTimeout OBJECT-TYPE
	SYNTAX Integer32 (0..65535)
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The minimum seconds before trigger actions can be repeated
		for  this auto-response."
	::= { ogCheckEntry 3 }

ogCheckResetTimeout OBJECT-TYPE
	SYNTAX Integer32 (0..65535)
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The minimum seconds after resolution before this
		auto-response can be triggered again."
	::= { ogCheckEntry 4 }

ogCheckType OBJECT-TYPE
 	SYNTAX INTEGER {
 		unknown(1),
 		serialSignal(2),
 		serialUser(3),
 		serialPattern(4),
		hostPing(5),
		hostService(6),
		hostUser(7),
 		webUser(8),
 		envTemperature(9),
 		envHumidity(10),
 		dioInput(11),
 		netInterface(12),
 		powerSupplyInputVoltage(13),
 		powerSupplyOutputCurrent(14),
 		powerSupplyTemperature(15),
 		upsInputVoltage(16),
 		upsBatteryCharge(17),
 		upsBatteryTemperature(18),
 		upsOutputLoad(19),
 		upsInputFrequency(20),
 		upsStateOnBattery(21),
 		upsStateLowBattery(22),
 		rpcInput(23),
 		rpcOutletState(24),
 		rpcOutletOutput(25),
 		cellMessage(26),
 		cellData(27),
 		cellSignal(28),
 		cellApn(29),
 		cellTower(30),
 		cellNetwork(31),
 		wirelessClientConnect(32),
 		wirelessClientSignal(33),
 		wirelessApAssociation(34),
 		wirelessApAuthentication(35),
 		dialPoolHealth(36),
 		cliUser(37),
		custom(255)
 	}
 	MAX-ACCESS read-only
 	STATUS current
 	DESCRIPTION
 	        "The auto-response check type"
 	::= { ogCheckEntry 5 }

ogCheckTriggerActions OBJECT-TYPE
 	SYNTAX Counter32
 	MAX-ACCESS read-only
 	STATUS current
 	DESCRIPTION
 		"The number of Trigger Actions configured for the auto-response."
 	::= { ogCheckEntry 6 }

ogCheckResolveActions OBJECT-TYPE
 	SYNTAX Counter32
 	MAX-ACCESS read-only
 	STATUS current
 	DESCRIPTION
 		"The number of Resolve Actions configured for the auto-response."
 	::= { ogCheckEntry 7 }

ogCheckDeviceTable OBJECT-TYPE
	SYNTAX SEQUENCE OF CheckDeviceEntry
	MAX-ACCESS not-accessible
	STATUS     current
	DESCRIPTION
           "The auto-response device reference table."
	::= { ogStatus2 22 }

ogCheckDeviceEntry OBJECT-TYPE
	SYNTAX CheckDeviceEntry
	MAX-ACCESS not-accessible
	STATUS current
	DESCRIPTION
		"RPC Outlet status entry"
	INDEX { ogCheckIndex,
		ogCheckDeviceIndex }
	::= { ogCheckDeviceTable 1 }

CheckDeviceEntry ::= SEQUENCE {
        ogCheckDeviceIndex Integer32,
        ogCheckDeviceCheck OBJECT IDENTIFIER,
        ogCheckDeviceName  DisplayString,
        ogCheckDeviceRef   DisplayString
}

ogCheckDeviceIndex OBJECT-TYPE
	SYNTAX Integer32 (0..65535)
	MAX-ACCESS not-accessible
	STATUS current
	DESCRIPTION
		"Index within the auto-response device outlet table"
	::= { ogCheckDeviceEntry 1 }

ogCheckDeviceCheck OBJECT-TYPE
	SYNTAX OBJECT IDENTIFIER
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The check this device is associated with."
	::= { ogCheckDeviceEntry 2 }


ogCheckDeviceName OBJECT-TYPE
	SYNTAX DisplayString (SIZE (0..255))
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The name of a device pertaining to the auto-reponse."
	::= { ogCheckDeviceEntry 3 }

ogCheckDeviceRef OBJECT-TYPE
	SYNTAX DisplayString (SIZE (0..255))
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The reference ID of the device pertaining to the auto-reponse."
	::= { ogCheckDeviceEntry 4 }

--
-- The Alarm Group
--
ogAlarm OBJECT IDENTIFIER ::= { ogStatus2 23 }

ogAlarmLogTable OBJECT-TYPE
	SYNTAX  SEQUENCE OF AlarmLogEntry
        MAX-ACCESS not-accessible
        STATUS     current
 	DESCRIPTION
            "The alarm history table."
 	::= { ogAlarm 1 }

 ogAlarmLogEntry OBJECT-TYPE
 	SYNTAX AlarmLogEntry
 	MAX-ACCESS not-accessible
 	STATUS current
 	DESCRIPTION
 		"An alarm entry."
 	INDEX { ogAlarmLogIndex }
 	::= { ogAlarmLogTable 1 }

AlarmLogEntry ::= SEQUENCE {
 	ogAlarmLogIndex      Integer32,
 	ogAlarmEventId       Integer32,
 	ogAlarmName          DisplayString,
 	ogAlarmCheck         Integer32,
 	ogAlarmInstance      Integer32,
 	ogAlarmTime          DateAndTime,
 	ogAlarmType          INTEGER,
 	ogAlarmSummary       DisplayString,
 	ogAlarmDevice        DisplayString,
 	ogAlarmUser          DisplayString,
 	ogAlarmTriggerValue  Integer32,
 	ogAlarmCurrentValue  Integer32,
 	ogAlarmPreviousValue Integer32,
	ogAlarmState         INTEGER
}

ogAlarmLogIndex OBJECT-TYPE
 	SYNTAX Integer32 (0..65535)
 	MAX-ACCESS not-accessible
 	STATUS current
 	DESCRIPTION
 		"Index within the current alarm table of this alarm."
 	::= { ogAlarmLogEntry 1 }

ogAlarmEventId OBJECT-TYPE
 	SYNTAX Integer32
 	MAX-ACCESS read-only
 	STATUS current
 	DESCRIPTION
 		"Unique event ID for this alarm."
 	::= { ogAlarmLogEntry 2 }

ogAlarmName OBJECT-TYPE
	SYNTAX DisplayString (SIZE (0..32))
 	MAX-ACCESS read-only
 	STATUS current
 	DESCRIPTION
 		"The check ID that this alarm pertains to."
 	::= { ogAlarmLogEntry 3 }

ogAlarmCheck OBJECT-TYPE
	SYNTAX Integer32
 	MAX-ACCESS read-only
 	STATUS current
 	DESCRIPTION
 		"The auto-response index this alarm relates to."
 	::= { ogAlarmLogEntry 4 }

ogAlarmInstance OBJECT-TYPE
	SYNTAX Integer32
 	MAX-ACCESS read-only
 	STATUS current
 	DESCRIPTION
 		"The reference index for this alarm instance."
 	::= { ogAlarmLogEntry 5 }

ogAlarmTime OBJECT-TYPE
 	SYNTAX DateAndTime
 	MAX-ACCESS read-only
 	STATUS current
 	DESCRIPTION
 		"The UTC date and time for when this alarm was created."
 	::= { ogAlarmLogEntry 6 }

ogAlarmType OBJECT-TYPE
 	SYNTAX INTEGER {
		serialSignalCts(1),
		serialSignalDcd(2),
		serialSignalDsr(3),
		serialPatternTx(4),
		serialPatternRx(5),
		serialUserSession(6),
		hostPingDown(7),
		hostPingUp(8),
		hostServiceDown(9),
		hostServiceUp(10),
		hostUserSession(11),
		webUserSession(12),
		envTemperatureLow(13),
		envTemperatureHigh(14),
		envHumidityLow(15),
		envHumidityHigh(16),
		dioSignalOpened(17),
		dioSignalClosed(18),
		netInterfaceDown(19),
		netInterfaceStarting(20),
		netInterfaceUp(21),
		netInterfaceStopping(22),
		powerSupplyInputVoltageLow(23),
		powerSupplyInputVoltageHigh(24),
		powerSupplyOutputCurrentLow(25),
		powerSupplyOutputCurrentHigh(26),
		powerSupplyTemperatureLow(27),
		powerSupplyTemperatureHigh(28),
		upsTemperatureHigh(29),
		upsTemperatureLow(30),
		upsHumidityHigh(31),
		upsHumidityLow(32),
		upsOnBattery(33),
		upsLowBattery(34),
		upsBatteryChargeLow(35),
		upsBatteryChargeHigh(36),
		upsBatteryVoltageLow(37),
		upsBatteryVoltageHigh(38),
		upsBatteryCurrentLow(39),
		upsBatteryCurrentHigh(40),
		upsBatteryTemperatureLow(41),
		upsBatteryTemperatureHigh(42),
		upsInputFrequencyLow(43),
		upsInputFrequencyHigh(44),
		upsInputVoltageLow(45),
		upsInputVoltageHigh(46),
		upsInputCurrentLow(47),
		upsInputCurrentHigh(48),
		upsOutputFrequencyLow(49),
		upsOutputFrequencyHigh(50),
		upsOutputVoltageLow(51),
		upsOutputVoltageHigh(52),
		upsOutputCurrentLow(53),
		upsOutputCurrentHigh(54),
		upsOutputLoadLow(55),
		upsOutputLoadHigh(56),
		upsOutputPowerLow(57),
		upsOutputPowerHigh(58),
		upsOutputTruePowerLow(59),
		upsOutputTruePowerHigh(60),
		rpcInputFrequencyLow(61),
		rpcInputFrequencyHigh(62),
		rpcInputVoltageLow(63),
		rpcInputVoltageHigh(64),
		rpcInputCurrentLow(65),
		rpcInputCurrentHigh(66),
		rpcOutletFrequencyHigh(67),
		rpcOutletFrequencyLow(68),
		rpcOutletVoltageHigh(69),
		rpcOutletVoltageLow(70),
		rpcOutletCurrentHigh(71),
		rpcOutletCurrentLow(72),
		rpcOutletStateOff(73),
		rpcOutletStateOn(74),
		cellDataUsage(75),
		cellMessageReceived(76),
		cellSignalLow(77),
		cellSignalHigh(78),
		cellApnChanged(79),
		cellTowerChanged(80),
		cellNetworkChanged(81),
		wirelessClientConnected(82),
		wirelessClientDisconnected(83),
		wirelessClientSignalLow(84),
		wirelessClientSignalHigh(85),
		wirelessApAssociation(86),
		wirelessApDisassociation(87),
		wirelessApAuthenticationFailure(88),
		dialPoolHealth(89),
		cliUserSession(90),
		customCheckFailure(255),
		unknown(65535)
	}
 	MAX-ACCESS read-only
 	STATUS current
 	DESCRIPTION
 		"A reference to an Alarm Type Object."
 	::= { ogAlarmLogEntry 7 }

ogAlarmSummary OBJECT-TYPE
 	SYNTAX DisplayString
 	MAX-ACCESS read-only
 	STATUS current
 	DESCRIPTION
 		"The human readable summary of this alarm."
 	::= { ogAlarmLogEntry 8 }

ogAlarmDevice OBJECT-TYPE
 	SYNTAX DisplayString
 	MAX-ACCESS read-only
 	STATUS current
 	DESCRIPTION
 		"The device ID that this alarm pertains to."
 	::= { ogAlarmLogEntry 9 }

ogAlarmUser OBJECT-TYPE
 	SYNTAX DisplayString
 	MAX-ACCESS read-only
 	STATUS current
 	DESCRIPTION
 		"The user ID that this alarm pertains to."
 	::= { ogAlarmLogEntry 10 }

ogAlarmTriggerValue OBJECT-TYPE
	SYNTAX Integer32
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The threshold value which triggers the alarm."
	::= { ogAlarmLogEntry 11 }

ogAlarmCurrentValue OBJECT-TYPE
	SYNTAX Integer32
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The value as of the time of this entry."
	::= { ogAlarmLogEntry 12 }

ogAlarmPreviousValue OBJECT-TYPE
	SYNTAX Integer32
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The former value of this entry."
	::= { ogAlarmLogEntry 13 }

ogAlarmState OBJECT-TYPE
 	SYNTAX INTEGER {
		normal(1),
		triggered(2),
		resolving(3),
		waiting(4),
		disabled(5),
		unresolvable(6)
	}
 	MAX-ACCESS read-only
 	STATUS current
 	DESCRIPTION
 		"The effective alarm state."
 	::= { ogAlarmLogEntry 14 }

ogCurrentAlarmTable OBJECT-TYPE
	SYNTAX  SEQUENCE OF CurrentAlarmEntry
        MAX-ACCESS not-accessible
        STATUS     current
 	DESCRIPTION
            "The alarm history table."
 	::= { ogAlarm 2 }

ogCurrentAlarmEntry OBJECT-TYPE
 	SYNTAX CurrentAlarmEntry
 	MAX-ACCESS not-accessible
 	STATUS current
 	DESCRIPTION
 		"An alarm entry."
 	INDEX { ogCurrentAlarmIndex }
 	::= { ogCurrentAlarmTable 1 }

CurrentAlarmEntry ::= SEQUENCE {
 	ogCurrentAlarmIndex         Integer32,
 	ogCurrentAlarmEventId       Integer32,
 	ogCurrentAlarmName          DisplayString,
 	ogCurrentAlarmCheck         Integer32,
 	ogCurrentAlarmInstance      Integer32,
 	ogCurrentAlarmTime          DateAndTime,
 	ogCurrentAlarmType          INTEGER,
 	ogCurrentAlarmSummary       DisplayString,
 	ogCurrentAlarmDevice        DisplayString,
 	ogCurrentAlarmUser          DisplayString,
 	ogCurrentAlarmTriggerValue  Integer32,
 	ogCurrentAlarmCurrentValue  Integer32,
 	ogCurrentAlarmPreviousValue Integer32,
 	ogCurrentAlarmState         INTEGER
}

ogCurrentAlarmIndex OBJECT-TYPE
 	SYNTAX Integer32 (0..65535)
 	MAX-ACCESS not-accessible
 	STATUS current
 	DESCRIPTION
 		"Index within the current alarm table of this alarm."
 	::= { ogCurrentAlarmEntry 1 }

ogCurrentAlarmEventId OBJECT-TYPE
 	SYNTAX Integer32
 	MAX-ACCESS read-only
 	STATUS current
 	DESCRIPTION
 		"Unique event ID for this alarm."
 	::= { ogCurrentAlarmEntry 2 }

ogCurrentAlarmName OBJECT-TYPE
	SYNTAX DisplayString (SIZE (0..32))
 	MAX-ACCESS read-only
 	STATUS current
 	DESCRIPTION
 		"The ID of the check this alarm pertains to."
 	::= { ogCurrentAlarmEntry 3 }

ogCurrentAlarmCheck OBJECT-TYPE
	SYNTAX Integer32
 	MAX-ACCESS read-only
 	STATUS current
 	DESCRIPTION
 		"The auto-response index this alarm relates to."
 	::= { ogCurrentAlarmEntry 4 }

ogCurrentAlarmInstance OBJECT-TYPE
	SYNTAX Integer32
 	MAX-ACCESS read-only
 	STATUS current
 	DESCRIPTION
 		"The reference index for this alarm instance."
 	::= { ogCurrentAlarmEntry 5 }

ogCurrentAlarmTime OBJECT-TYPE
 	SYNTAX DateAndTime
 	MAX-ACCESS read-only
 	STATUS current
 	DESCRIPTION
 		"The UTC date and time for when this alarm was created."
 	::= { ogCurrentAlarmEntry 6 }

ogCurrentAlarmType OBJECT-TYPE
 	SYNTAX INTEGER {
		serialSignalCts(1),
		serialSignalDcd(2),
		serialSignalDsr(3),
		serialPatternTx(4),
		serialPatternRx(5),
		serialUserSession(6),
		hostPingDown(7),
		hostPingUp(8),
		hostServiceDown(9),
		hostServiceUp(10),
		hostUserSession(11),
		webUserSession(12),
		envTemperatureLow(13),
		envTemperatureHigh(14),
		envHumidityLow(15),
		envHumidityHigh(16),
		dioSignalOpened(17),
		dioSignalClosed(18),
		netInterfaceDown(19),
		netInterfaceStarting(20),
		netInterfaceUp(21),
		netInterfaceStopping(22),
		powerSupplyInputVoltageLow(23),
		powerSupplyInputVoltageHigh(24),
		powerSupplyOutputCurrentLow(25),
		powerSupplyOutputCurrentHigh(26),
		powerSupplyTemperatureLow(27),
		powerSupplyTemperatureHigh(28),
		upsTemperatureHigh(29),
		upsTemperatureLow(30),
		upsHumidityHigh(31),
		upsHumidityLow(32),
		upsOnBattery(33),
		upsLowBattery(34),
		upsBatteryChargeLow(35),
		upsBatteryChargeHigh(36),
		upsBatteryVoltageLow(37),
		upsBatteryVoltageHigh(38),
		upsBatteryCurrentLow(39),
		upsBatteryCurrentHigh(40),
		upsBatteryTemperatureLow(41),
		upsBatteryTemperatureHigh(42),
		upsInputFrequencyLow(43),
		upsInputFrequencyHigh(44),
		upsInputVoltageLow(45),
		upsInputVoltageHigh(46),
		upsInputCurrentLow(47),
		upsInputCurrentHigh(48),
		upsOutputFrequencyLow(49),
		upsOutputFrequencyHigh(50),
		upsOutputVoltageLow(51),
		upsOutputVoltageHigh(52),
		upsOutputCurrentLow(53),
		upsOutputCurrentHigh(54),
		upsOutputLoadLow(55),
		upsOutputLoadHigh(56),
		upsOutputPowerLow(57),
		upsOutputPowerHigh(58),
		upsOutputTruePowerLow(59),
		upsOutputTruePowerHigh(60),
		rpcInputFrequencyLow(61),
		rpcInputFrequencyHigh(62),
		rpcInputVoltageLow(63),
		rpcInputVoltageHigh(64),
		rpcInputCurrentLow(65),
		rpcInputCurrentHigh(66),
		rpcOutletFrequencyHigh(67),
		rpcOutletFrequencyLow(68),
		rpcOutletVoltageHigh(69),
		rpcOutletVoltageLow(70),
		rpcOutletCurrentHigh(71),
		rpcOutletCurrentLow(72),
		rpcOutletStateOff(73),
		rpcOutletStateOn(74),
		cellDataUsage(75),
		cellMessageReceived(76),
		cellSignalLow(77),
		cellSignalHigh(78),
		cellApnChanged(79),
		cellTowerChanged(80),
		cellNetworkChanged(81),
		wirelessClientConnected(82),
		wirelessClientDisconnected(83),
		wirelessClientSignalLow(84),
		wirelessClientSignalHigh(85),
		wirelessApAssociation(86),
		wirelessApDisassociation(87),
		wirelessApAuthenticationFailure(88),
		dialPoolHealth(89),
		cliUserSession(90),
		customCheckFailure(255),
		unknown(65535)
	}
 	MAX-ACCESS read-only
 	STATUS current
 	DESCRIPTION
 		"The specific Alarm Type."
 	::= { ogCurrentAlarmEntry 7 }

ogCurrentAlarmSummary OBJECT-TYPE
 	SYNTAX DisplayString
 	MAX-ACCESS read-only
 	STATUS current
 	DESCRIPTION
 		"A readable summary of this alarm."
 	::= { ogCurrentAlarmEntry 8 }

ogCurrentAlarmDevice OBJECT-TYPE
 	SYNTAX DisplayString
 	MAX-ACCESS read-only
 	STATUS current
 	DESCRIPTION
 		"The ID of the device this alarm pertains to."
 	::= { ogCurrentAlarmEntry 9 }

ogCurrentAlarmUser OBJECT-TYPE
 	SYNTAX DisplayString
 	MAX-ACCESS read-only
 	STATUS current
 	DESCRIPTION
 		"The ID of the user this alarm pertains to."
 	::= { ogCurrentAlarmEntry 10 }

ogCurrentAlarmTriggerValue OBJECT-TYPE
	SYNTAX Integer32
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The threshold value which triggers the alarm."
	::= { ogCurrentAlarmEntry 11 }

ogCurrentAlarmCurrentValue OBJECT-TYPE
	SYNTAX Integer32
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The value as of the time of this entry."
	::= { ogCurrentAlarmEntry 12 }

ogCurrentAlarmPreviousValue OBJECT-TYPE
	SYNTAX Integer32
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The former value of this entry."
	::= { ogCurrentAlarmEntry 13 }

ogCurrentAlarmState OBJECT-TYPE
 	SYNTAX INTEGER {
		normal(1),
		triggered(2),
		resolving(3),
		waiting(4),
		disabled(5),
		unresolvable(6)
	}
	MAX-ACCESS read-only
	STATUS current
	DESCRIPTION
		"The effective alarm state."
	::= { ogCurrentAlarmEntry 14 }

-- Notifications
ogStatus2NotificationPrefix OBJECT IDENTIFIER ::= {
 	ogStatus2 100
}

ogMibNotifications OBJECT IDENTIFIER ::= {
	ogStatus2NotificationPrefix 0
}

ogSerialSignalNotification NOTIFICATION-TYPE
 	OBJECTS {
		ogAlarmEventId,
		ogAlarmName,
		ogAlarmCheck,
		ogAlarmInstance,
		ogAlarmTime,
		ogAlarmType,
		ogAlarmSummary,
		ogAlarmDevice,
		ogAlarmUser,
		ogAlarmTriggerValue,
		ogAlarmCurrentValue,
		ogAlarmPreviousValue,
		ogAlarmState
	}
	STATUS current
	DESCRIPTION
		"The notification sent when a serial signal changes."
	::= { ogMibNotifications 1 }

ogSerialPatternNotification NOTIFICATION-TYPE
 	OBJECTS {
		ogAlarmEventId,
		ogAlarmName,
		ogAlarmCheck,
		ogAlarmInstance,
		ogAlarmTime,
		ogAlarmType,
		ogAlarmSummary,
		ogAlarmDevice,
		ogAlarmUser,
		ogAlarmTriggerValue,
		ogAlarmCurrentValue,
		ogAlarmPreviousValue,
		ogAlarmState
	}
 	STATUS current
 	DESCRIPTION
 		"The notification sent when a pattern is matched on a serial
		port ."
 	::= { ogMibNotifications 2 }

ogSerialUserNotification NOTIFICATION-TYPE
 	OBJECTS {
		ogAlarmEventId,
		ogAlarmName,
		ogAlarmCheck,
		ogAlarmInstance,
		ogAlarmTime,
		ogAlarmType,
		ogAlarmSummary,
		ogAlarmDevice,
		ogAlarmUser,
		ogAlarmTriggerValue,
		ogAlarmCurrentValue,
		ogAlarmPreviousValue,
		ogAlarmState
	}
	STATUS current
	DESCRIPTION
 		"The notification sent when a user logs in or out of a serial
		console."
	::= { ogMibNotifications 3 }

ogHostPingNotification NOTIFICATION-TYPE
 	OBJECTS {
		ogAlarmEventId,
		ogAlarmName,
		ogAlarmCheck,
		ogAlarmInstance,
		ogAlarmTime,
		ogAlarmType,
		ogAlarmSummary,
		ogAlarmDevice,
		ogAlarmUser,
		ogAlarmTriggerValue,
		ogAlarmCurrentValue,
		ogAlarmPreviousValue,
		ogAlarmState
	}
 	STATUS current
 	DESCRIPTION
 		"The notification sent when a host stops or resumes responding
		to a ping."
 	::= { ogMibNotifications 4 }

ogHostServiceNotification NOTIFICATION-TYPE
 	OBJECTS {
		ogAlarmEventId,
		ogAlarmName,
		ogAlarmCheck,
		ogAlarmInstance,
		ogAlarmTime,
		ogAlarmType,
		ogAlarmSummary,
		ogAlarmDevice,
		ogAlarmUser,
		ogAlarmTriggerValue,
		ogAlarmCurrentValue,
		ogAlarmPreviousValue,
		ogAlarmState
	}
 	STATUS current
 	DESCRIPTION
 		"The notification sent when a host service stops or resumes."
 	::= { ogMibNotifications 5 }

ogHostUserNotification NOTIFICATION-TYPE
 	OBJECTS {
		ogAlarmEventId,
		ogAlarmName,
		ogAlarmCheck,
		ogAlarmInstance,
		ogAlarmTime,
		ogAlarmType,
		ogAlarmSummary,
		ogAlarmDevice,
		ogAlarmUser,
		ogAlarmTriggerValue,
		ogAlarmCurrentValue,
		ogAlarmPreviousValue,
		ogAlarmState
	}
 	STATUS current
 	DESCRIPTION
 		"The notification sent when a user logs in or out of a network
		host."
 	::= { ogMibNotifications 6 }

ogWebUserNotification NOTIFICATION-TYPE
 	OBJECTS {
		ogAlarmEventId,
		ogAlarmName,
		ogAlarmCheck,
		ogAlarmInstance,
		ogAlarmTime,
		ogAlarmType,
		ogAlarmSummary,
		ogAlarmDevice,
		ogAlarmUser,
		ogAlarmTriggerValue,
		ogAlarmCurrentValue,
		ogAlarmPreviousValue,
		ogAlarmState
 	}
 	STATUS current
 	DESCRIPTION
 		"The notification sent when a user logs in or out of the web
		interface."
 	::= { ogMibNotifications 7 }


ogEmdTemperatureNotification NOTIFICATION-TYPE
 	OBJECTS {
		ogAlarmEventId,
		ogAlarmName,
		ogAlarmCheck,
		ogAlarmInstance,
		ogAlarmTime,
		ogAlarmType,
		ogAlarmSummary,
		ogAlarmDevice,
		ogAlarmUser,
		ogAlarmTriggerValue,
		ogAlarmCurrentValue,
		ogAlarmPreviousValue,
		ogAlarmState
 	}
 	STATUS current
 	DESCRIPTION
 		"The notification sent when a temperature event occurs"
 	::= { ogMibNotifications 8 }

ogEmdHumidityNotification NOTIFICATION-TYPE
 	OBJECTS {
		ogAlarmEventId,
		ogAlarmName,
		ogAlarmCheck,
		ogAlarmInstance,
		ogAlarmTime,
		ogAlarmType,
		ogAlarmSummary,
		ogAlarmDevice,
		ogAlarmUser,
		ogAlarmTriggerValue,
		ogAlarmCurrentValue,
		ogAlarmPreviousValue,
		ogAlarmState
 	}
 	STATUS current
 	DESCRIPTION
 		"The notification sent when a humidity event occurs"
 	::= { ogMibNotifications 9 }

ogEmdDioNotification NOTIFICATION-TYPE
 	OBJECTS {
		ogAlarmEventId,
		ogAlarmName,
		ogAlarmCheck,
		ogAlarmInstance,
		ogAlarmTime,
		ogAlarmType,
		ogAlarmSummary,
		ogAlarmDevice,
		ogAlarmUser,
		ogAlarmTriggerValue,
		ogAlarmCurrentValue,
		ogAlarmPreviousValue,
		ogAlarmState
 	}
 	STATUS current
 	DESCRIPTION
 		"The notification sent when a Digital I/O input event occurs"
 	::= { ogMibNotifications 10 }

ogPowerSupplyInputNotification NOTIFICATION-TYPE
 	OBJECTS {
		ogAlarmEventId,
		ogAlarmName,
		ogAlarmCheck,
		ogAlarmInstance,
		ogAlarmTime,
		ogAlarmType,
		ogAlarmSummary,
		ogAlarmDevice,
		ogAlarmUser,
		ogAlarmTriggerValue,
		ogAlarmCurrentValue,
		ogAlarmPreviousValue,
		ogAlarmState
 	}
 	STATUS current
 	DESCRIPTION
 		"The notification sent when a power supply voltage alarm occurs"
 	::= { ogMibNotifications 11 }

ogPowerSupplyOutputNotification NOTIFICATION-TYPE
 	OBJECTS {
		ogAlarmEventId,
		ogAlarmName,
		ogAlarmCheck,
		ogAlarmInstance,
		ogAlarmTime,
		ogAlarmType,
		ogAlarmSummary,
		ogAlarmDevice,
		ogAlarmUser,
		ogAlarmTriggerValue,
		ogAlarmCurrentValue,
		ogAlarmPreviousValue,
		ogAlarmState
 	}
 	STATUS current
 	DESCRIPTION
 		"The notification sent when a power supply voltage alarm occurs"
 	::= { ogMibNotifications 12 }

ogPowerSupplyTempNotification NOTIFICATION-TYPE
 	OBJECTS {
		ogAlarmEventId,
		ogAlarmName,
		ogAlarmCheck,
		ogAlarmInstance,
		ogAlarmTime,
		ogAlarmType,
		ogAlarmSummary,
		ogAlarmDevice,
		ogAlarmUser,
		ogAlarmTriggerValue,
		ogAlarmCurrentValue,
		ogAlarmPreviousValue,
		ogAlarmState
 	}
 	STATUS current
 	DESCRIPTION
 		"The notification sent when a power supply voltage alarm occurs"
 	::= { ogMibNotifications 13 }

ogUpsNotification NOTIFICATION-TYPE
 	OBJECTS {
		ogAlarmEventId,
		ogAlarmName,
		ogAlarmCheck,
		ogAlarmInstance,
		ogAlarmTime,
		ogAlarmType,
		ogAlarmSummary,
		ogAlarmDevice,
		ogAlarmUser,
		ogAlarmTriggerValue,
		ogAlarmCurrentValue,
		ogAlarmPreviousValue,
		ogAlarmState
 	}
 	STATUS current
 	DESCRIPTION
 		"The notification sent when a UPS alarm occurs"
 	::= { ogMibNotifications 14 }

ogUpsBatteryNotification NOTIFICATION-TYPE
 	OBJECTS {
		ogAlarmEventId,
		ogAlarmName,
		ogAlarmCheck,
		ogAlarmInstance,
		ogAlarmTime,
		ogAlarmType,
		ogAlarmSummary,
		ogAlarmDevice,
		ogAlarmUser,
		ogAlarmTriggerValue,
		ogAlarmCurrentValue,
		ogAlarmPreviousValue,
		ogAlarmState
 	}
 	STATUS current
 	DESCRIPTION
 		"The notification sent when a UPS battery alarm occurs"
 	::= { ogMibNotifications 15 }

ogUpsInputNotification NOTIFICATION-TYPE
 	OBJECTS {
		ogAlarmEventId,
		ogAlarmName,
		ogAlarmCheck,
		ogAlarmInstance,
		ogAlarmTime,
		ogAlarmType,
		ogAlarmSummary,
		ogAlarmDevice,
		ogAlarmUser,
		ogAlarmTriggerValue,
		ogAlarmCurrentValue,
		ogAlarmPreviousValue,
		ogAlarmState
 	}
 	STATUS current
 	DESCRIPTION
 		"The notification sent when a UPS input alarm occurs"
 	::= { ogMibNotifications 16 }

ogUpsOutputNotification NOTIFICATION-TYPE
 	OBJECTS {
		ogAlarmEventId,
		ogAlarmName,
		ogAlarmCheck,
		ogAlarmInstance,
		ogAlarmTime,
		ogAlarmType,
		ogAlarmSummary,
		ogAlarmDevice,
		ogAlarmUser,
		ogAlarmTriggerValue,
		ogAlarmCurrentValue,
		ogAlarmPreviousValue,
		ogAlarmState
 	}
 	STATUS current
 	DESCRIPTION
 		"The notification sent when a UPS output alarm occurs"
 	::= { ogMibNotifications 17 }

ogRpcInputNotification NOTIFICATION-TYPE
 	OBJECTS {
		ogAlarmEventId,
		ogAlarmName,
		ogAlarmCheck,
		ogAlarmInstance,
		ogAlarmTime,
		ogAlarmType,
		ogAlarmSummary,
		ogAlarmDevice,
		ogAlarmUser,
		ogAlarmTriggerValue,
		ogAlarmCurrentValue,
		ogAlarmPreviousValue,
		ogAlarmState
 	}
 	STATUS current
 	DESCRIPTION
 		"The notification sent when a RPC input alarm occurs"
 	::= { ogMibNotifications 18 }

ogRpcOutputNotification NOTIFICATION-TYPE
 	OBJECTS {
		ogAlarmEventId,
		ogAlarmName,
		ogAlarmCheck,
		ogAlarmInstance,
		ogAlarmTime,
		ogAlarmType,
		ogAlarmSummary,
		ogAlarmDevice,
		ogAlarmUser,
		ogAlarmTriggerValue,
		ogAlarmCurrentValue,
		ogAlarmPreviousValue,
		ogAlarmState
 	}
 	STATUS current
 	DESCRIPTION
 		"The notification sent when a RPC output alarm occurs"
 	::= { ogMibNotifications 19 }

ogRpcOutletNotification NOTIFICATION-TYPE
 	OBJECTS {
		ogAlarmEventId,
		ogAlarmName,
		ogAlarmCheck,
		ogAlarmInstance,
		ogAlarmTime,
		ogAlarmType,
		ogAlarmSummary,
		ogAlarmDevice,
		ogAlarmUser,
		ogAlarmTriggerValue,
		ogAlarmCurrentValue,
		ogAlarmPreviousValue,
		ogAlarmState
 	}
 	STATUS current
 	DESCRIPTION
 		"The notification sent when a RPC output alarm occurs"
 	::= { ogMibNotifications 20 }


ogNetInterfaceNotification NOTIFICATION-TYPE
 	OBJECTS {
		ogAlarmEventId,
		ogAlarmName,
		ogAlarmCheck,
		ogAlarmInstance,
		ogAlarmTime,
		ogAlarmType,
		ogAlarmSummary,
		ogAlarmDevice,
		ogAlarmUser,
		ogAlarmTriggerValue,
		ogAlarmCurrentValue,
		ogAlarmPreviousValue,
		ogAlarmState
 	}
 	STATUS current
 	DESCRIPTION
 		"The notification sent when a network interface event occurs."
 	::= { ogMibNotifications 21 }

ogCellDataNotification NOTIFICATION-TYPE
 	OBJECTS {
		ogAlarmEventId,
		ogAlarmName,
		ogAlarmCheck,
		ogAlarmInstance,
		ogAlarmTime,
		ogAlarmType,
		ogAlarmSummary,
		ogAlarmDevice,
		ogAlarmUser,
		ogAlarmTriggerValue,
		ogAlarmCurrentValue,
		ogAlarmPreviousValue,
		ogAlarmState
 	}
 	STATUS current
 	DESCRIPTION
 		"The notification sent when a cellular data alarm occurs."
 	::= { ogMibNotifications 22 }

ogCellMessageNotification NOTIFICATION-TYPE
 	OBJECTS {
		ogAlarmEventId,
		ogAlarmName,
		ogAlarmCheck,
		ogAlarmInstance,
		ogAlarmTime,
		ogAlarmType,
		ogAlarmSummary,
		ogAlarmDevice,
		ogAlarmUser,
		ogAlarmTriggerValue,
		ogAlarmCurrentValue,
		ogAlarmPreviousValue,
		ogAlarmState
 	}
 	STATUS current
 	DESCRIPTION
 		"The notification sent when an SMS command alarm occurs."
 	::= { ogMibNotifications 23 }

ogCellSignalNotification NOTIFICATION-TYPE
 	OBJECTS {
		ogAlarmEventId,
		ogAlarmName,
		ogAlarmCheck,
		ogAlarmInstance,
		ogAlarmTime,
		ogAlarmType,
		ogAlarmSummary,
		ogAlarmDevice,
		ogAlarmUser,
		ogAlarmTriggerValue,
		ogAlarmCurrentValue,
		ogAlarmPreviousValue,
		ogAlarmState
 	}
 	STATUS current
 	DESCRIPTION
 		"The notification sent when a cellular signal alarm occurs."
 	::= { ogMibNotifications 24 }

ogCellApnNotification NOTIFICATION-TYPE
 	OBJECTS {
		ogAlarmEventId,
		ogAlarmName,
		ogAlarmCheck,
		ogAlarmInstance,
		ogAlarmTime,
		ogAlarmType,
		ogAlarmSummary,
		ogAlarmDevice,
		ogAlarmUser,
		ogAlarmTriggerValue,
		ogAlarmCurrentValue,
		ogAlarmPreviousValue,
		ogAlarmState
 	}
 	STATUS current
 	DESCRIPTION
 		"The notification sent when a cellular APN alarm occurs."
 	::= { ogMibNotifications 25 }

ogCellTowerNotification NOTIFICATION-TYPE
 	OBJECTS {
		ogAlarmEventId,
		ogAlarmName,
		ogAlarmCheck,
		ogAlarmInstance,
		ogAlarmTime,
		ogAlarmType,
		ogAlarmSummary,
		ogAlarmDevice,
		ogAlarmUser,
		ogAlarmTriggerValue,
		ogAlarmCurrentValue,
		ogAlarmPreviousValue,
		ogAlarmState
 	}
 	STATUS current
 	DESCRIPTION
 		"The notification sent when a cellular tower alarm occurs."
 	::= { ogMibNotifications 26 }

ogCellNetworkNotification NOTIFICATION-TYPE
 	OBJECTS {
		ogAlarmEventId,
		ogAlarmName,
		ogAlarmCheck,
		ogAlarmInstance,
		ogAlarmTime,
		ogAlarmType,
		ogAlarmSummary,
		ogAlarmDevice,
		ogAlarmUser,
		ogAlarmTriggerValue,
		ogAlarmCurrentValue,
		ogAlarmPreviousValue,
		ogAlarmState
 	}
 	STATUS current
 	DESCRIPTION
 		"The notification sent when a cellular network alarm occurs."
 	::= { ogMibNotifications 27 }

ogWifiClientConnectNotification NOTIFICATION-TYPE
 	OBJECTS {
		ogAlarmEventId,
		ogAlarmName,
		ogAlarmCheck,
		ogAlarmInstance,
		ogAlarmTime,
		ogAlarmType,
		ogAlarmSummary,
		ogAlarmDevice,
		ogAlarmUser,
		ogAlarmTriggerValue,
		ogAlarmCurrentValue,
		ogAlarmPreviousValue,
		ogAlarmState
 	}
 	STATUS current
 	DESCRIPTION
 		"The notification sent when a wireless client connects or
		disconnects."
 	::= { ogMibNotifications 28 }

ogWifiClientSignalNotification NOTIFICATION-TYPE
 	OBJECTS {
		ogAlarmEventId,
		ogAlarmName,
		ogAlarmCheck,
		ogAlarmInstance,
		ogAlarmTime,
		ogAlarmType,
		ogAlarmSummary,
		ogAlarmDevice,
		ogAlarmUser,
		ogAlarmTriggerValue,
		ogAlarmCurrentValue,
		ogAlarmPreviousValue,
		ogAlarmState
 	}
 	STATUS current
 	DESCRIPTION
 		"The notification sent when a wireless client signal changes."
 	::= { ogMibNotifications 29 }

ogWifiApAssociationNotification NOTIFICATION-TYPE
 	OBJECTS {
		ogAlarmEventId,
		ogAlarmName,
		ogAlarmCheck,
		ogAlarmInstance,
		ogAlarmTime,
		ogAlarmType,
		ogAlarmSummary,
		ogAlarmDevice,
		ogAlarmUser,
		ogAlarmTriggerValue,
		ogAlarmCurrentValue,
		ogAlarmPreviousValue,
		ogAlarmState
 	}
 	STATUS current
 	DESCRIPTION
 		"The notification sent when a wireless client connects or
		disconnects to this AP."
 	::= { ogMibNotifications 30 }

ogWifiApAuthNotification NOTIFICATION-TYPE
 	OBJECTS {
		ogAlarmEventId,
		ogAlarmName,
		ogAlarmCheck,
		ogAlarmInstance,
		ogAlarmTime,
		ogAlarmType,
		ogAlarmSummary,
		ogAlarmDevice,
		ogAlarmUser,
		ogAlarmTriggerValue,
		ogAlarmCurrentValue,
		ogAlarmPreviousValue,
		ogAlarmState
 	}
 	STATUS current
 	DESCRIPTION
 		"The notification sent when a wireless client fails to 
		authenticate with this AP."
 	::= { ogMibNotifications 31 }

ogDialPoolHealthNotification NOTIFICATION-TYPE
 	OBJECTS {
		ogAlarmEventId,
		ogAlarmName,
		ogAlarmCheck,
		ogAlarmInstance,
		ogAlarmTime,
		ogAlarmType,
		ogAlarmSummary,
		ogAlarmDevice,
		ogAlarmUser,
		ogAlarmTriggerValue,
		ogAlarmCurrentValue,
		ogAlarmPreviousValue,
		ogAlarmState
 	}
 	STATUS current
 	DESCRIPTION
 		"The notification sent when dial-pool health alarm occurs."
 	::= { ogMibNotifications 32 }

ogCustomNotification NOTIFICATION-TYPE
 	OBJECTS {
		ogAlarmEventId,
		ogAlarmName,
		ogAlarmCheck,
		ogAlarmInstance,
		ogAlarmTime,
		ogAlarmType,
		ogAlarmSummary,
		ogAlarmDevice,
		ogAlarmUser,
		ogAlarmTriggerValue,
		ogAlarmCurrentValue,
		ogAlarmPreviousValue,
		ogAlarmState
 	}
 	STATUS current
 	DESCRIPTION
 		"The notification sent when a custom check is triggered."
 	::= { ogMibNotifications 33 }

ogCliUserSessionNotification NOTIFICATION-TYPE
 	OBJECTS {
		ogAlarmEventId,
		ogAlarmName,
		ogAlarmCheck,
		ogAlarmInstance,
		ogAlarmTime,
		ogAlarmType,
		ogAlarmSummary,
		ogAlarmDevice,
		ogAlarmUser,
		ogAlarmTriggerValue,
		ogAlarmCurrentValue,
		ogAlarmPreviousValue,
		ogAlarmState
 	}
 	STATUS current
 	DESCRIPTION
 		"The notification sent when a user logs in or out of a CLI
		session."
 	::= { ogMibNotifications 34 }

-- End notifications

-- conformance information

ogStatus2Conformance OBJECT IDENTIFIER ::= { ogStatus2 65535 }
ogStatus2Compliances OBJECT IDENTIFIER ::= {
	ogStatus2Conformance 1 }
ogStatus2Groups OBJECT IDENTIFIER ::= {
	ogStatus2Conformance 2 }

-- compliance statements

ogStatus2Compliance MODULE-COMPLIANCE
    STATUS  current
    DESCRIPTION
            "The compliance statement for the Opengear status MIB."
    MODULE  -- this module
    MANDATORY-GROUPS {
	    ogBasicStatusGroup,
	    ogBasicAlarmGroup,
	    ogBasicNotificationGroup
    }

   ::= { ogStatus2Compliances 1 }

-- units of conformance

ogBasicStatusGroup OBJECT-GROUP
    OBJECTS {
	ogFirmwareVersion,
	ogSerialNumber,
	ogSerialPortLabel,
	ogSerialPortSpeed,
	ogSerialPortDataBits,
	ogSerialPortParity,
	ogSerialPortStopBits,
	ogSerialPortFlowControl,
	ogSerialPortMode,
	ogSerialPortLogLevel,
	ogSerialPortRxBytes,
	ogSerialPortTxBytes,
	ogSerialPortFramingErrors,
	ogSerialPortParityErrors,
	ogSerialPortOverrunErrors,
	ogSerialPortBreaks,
	ogSerialPortDCD,
	ogSerialPortDTR,
	ogSerialPortDSR,
	ogSerialPortCTS,
	ogSerialPortRTS,
	ogSerialUserStartTime,
	ogSerialUserPort,
	ogSerialUserLabel,
	ogSerialUserName,
        ogHostName,
        ogHostIpV4Address,
        ogHostIpV6Address,
        ogHostServiceHost,
        ogHostServiceType,
        ogHostServicePort,
        ogHostServiceStatus,
        ogHostServiceCounter,
        ogHostUserHost,
	ogHostUserStartTime,
	ogHostUserAddress,
	ogHostUserHostName,
	ogHostUserName,
	ogWebUserStartTime,
	ogWebUserName,
	ogWebUserSourceAddress,
	ogWebUserSourcePort,
	ogEmdName,
	ogEmdDescription,
	ogEmdEnabled,
	ogEmdLogEnabled,
	ogEmdConnectType,
	ogEmdTemperatureTotal,
	ogEmdHumidityTotal,
	ogEmdDioInputTotal,
	ogEmdTemperatureEmd,
	ogEmdTemperatureName,
	ogEmdTemperatureDescription,
	ogEmdTemperatureValue,
	ogEmdTemperatureCounter,
	ogEmdHumidityEmd,
	ogEmdHumidityName,
	ogEmdHumidityDescription,
	ogEmdHumidityValue,
	ogEmdHumidityCounter,
        ogEmdDioEmd,
        ogEmdDioName,
        ogEmdDioDescription,
        ogEmdDioType,
        ogEmdDioDirection,
        ogEmdDioState,
        ogEmdDioTriggerMode,
        ogEmdDioCounter,
	ogNetInterfaceName,
	ogNetInterfaceType,
	ogNetInterfaceState,
	ogPowerSupplyName,
	ogPowerSupplyInputVoltage,
	ogPowerSupplyOutputCurrent,
	ogPowerSupplyTemperature,
	ogUpsName,
        ogUpsDescription,
        ogUpsType,
        ogUpsLogEnabled,
        ogUpsConnectType,
        ogUpsState,
        ogUpsTemperature,
        ogUpsHumidity,
        ogUpsBatteryState,
        ogUpsBatteryRunTime,
        ogUpsBatteryRunTimeLow,
        ogUpsBatteryRunTimeRestart,
        ogUpsBatteryCharge,
        ogUpsBatteryVoltage,
        ogUpsBatteryNominalVoltage,
        ogUpsBatteryCurrent,
        ogUpsBatteryNominalCurrent,
        ogUpsBatteryTemperature,
        ogUpsInputFrequency,
        ogUpsInputNominalFrequency,
        ogUpsInputVoltage,
        ogUpsInputNominalVoltage,
        ogUpsInputCurrent,
        ogUpsInputNominalCurrent,
        ogUpsOutputFrequency,
        ogUpsOutputNominalFrequency,
        ogUpsOutputVoltage,
        ogUpsOutputNominalVoltage,
        ogUpsOutputCurrent,
        ogUpsOutputNominalCurrent,
        ogUpsOutputLoad,
        ogUpsOutputPower,
        ogUpsOutputTruePower,
        ogUpsCounter,
	ogRpcName,
	ogRpcDescription,
	ogRpcType,
	ogRpcLogEnabled,
	ogRpcOutletTotal,
	ogRpcMaxTemperature,
	ogRpcConnectType,
	ogRpcInputFrequency,
	ogRpcInputVoltage,
	ogRpcInputCurrent,
	ogRpcCounter,
	ogRpcOutletRpc,
	ogRpcOutletName,
	ogRpcOutletState,
	ogRpcOutletFrequency,
	ogRpcOutletCurrent,
	ogRpcOutletVoltage,
	ogRpcOutletLoad,
        ogCellModemVendor,
        ogCellModemModel,
        ogCellModemEnabled,
        ogCellModemConnected,
        ogCellModemNetwork,
        ogCellModemRegistered,
        ogCellModemTower,
        ogCellModemRadioTechnology,
        ogCellModemApn,
        ogCellModem3gRssi,
        ogCellModem4gRssi,
        ogCellModemSessionTime,
        ogCellModemSelectedSimCard,
        ogCellModemTemperature,
        ogCellModemCounter,
        ogCellModemIMSI,
        ogWifiClientInterface,
        ogWifiClientEnabled,
        ogWifiClientEssid,
        ogWifiClientIeeeMode,
        ogWifiClientMode,
        ogWifiClientFrequency,
        ogWifiClientApMac,
        ogWifiClientBitRate,
        ogWifiClientTxPower,
        ogWifiClientLinkQuality,
        ogWifiClientRssi,
        ogWifiClientRxInvalidNwid,
        ogWifiClientRxInvalidCrypt,
        ogWifiClientRxInvalidFrag,
        ogWifiClientRxInvalidRetries,
        ogWifiClientRxInvalidMisc,
        ogWifiClientMissedBeacon,
        ogWifiClientCounter,
        ogWifiApInterface,
        ogWifiApEnabled,
        ogWifiApSsid,
        ogWifiApIeeeMode,
        ogWifiApFrequency,
        ogWifiApTxPower,
        ogWifiApCounter,
        ogWifiApClientAp,
        ogWifiApClientMac,
        ogWifiApClientInactiveTime,
        ogWifiApClientRxBytes,
        ogWifiApClientRxPackets,
        ogWifiApClientTxBytes,
        ogWifiApClientTxPackets,
        ogWifiApClientRssi,
        ogWifiApClientTxBitRate,
	ogCheckName,
	ogCheckRepeatTimeout,
	ogCheckResetTimeout,
	ogCheckType,
	ogCheckTriggerActions,
	ogCheckResolveActions,
	ogCheckDeviceCheck,
	ogCheckDeviceName,
	ogCheckDeviceRef
    }
    STATUS  current
    DESCRIPTION
            "A collection of objects to retrieve Opengear statistics."
    ::= { ogStatus2Groups 1 }

ogBasicAlarmGroup OBJECT-GROUP
    OBJECTS {
	ogAlarmEventId,
	ogAlarmName,
	ogAlarmCheck,
	ogAlarmInstance,
	ogAlarmTime,
	ogAlarmType,
	ogAlarmSummary,
	ogAlarmDevice,
	ogAlarmUser,
	ogAlarmTriggerValue,
	ogAlarmCurrentValue,
	ogAlarmPreviousValue,
	ogAlarmState,
	ogCurrentAlarmEventId,
	ogCurrentAlarmName,
	ogCurrentAlarmCheck,
	ogCurrentAlarmInstance,
	ogCurrentAlarmTime,
	ogCurrentAlarmType,
	ogCurrentAlarmSummary,
	ogCurrentAlarmDevice,
	ogCurrentAlarmUser,
	ogCurrentAlarmTriggerValue,
	ogCurrentAlarmCurrentValue,
	ogCurrentAlarmPreviousValue,
	ogCurrentAlarmState
    }
    STATUS  current
    DESCRIPTION
            "A collection of objects to report Opengear alarms."
    ::= { ogStatus2Groups 2 }

ogBasicNotificationGroup NOTIFICATION-GROUP
       NOTIFICATIONS {
               ogSerialSignalNotification,
               ogSerialPatternNotification,
               ogSerialUserNotification,
               ogHostPingNotification,
               ogHostServiceNotification,
               ogHostUserNotification,
               ogWebUserNotification,
               ogEmdDioNotification,
               ogEmdTemperatureNotification,
               ogEmdHumidityNotification,
               ogPowerSupplyInputNotification,
               ogPowerSupplyOutputNotification,
               ogPowerSupplyTempNotification,
               ogUpsNotification,
               ogUpsInputNotification,
               ogUpsBatteryNotification,
               ogUpsOutputNotification,
               ogRpcInputNotification,
               ogRpcOutputNotification,
               ogRpcOutletNotification,
               ogNetInterfaceNotification,
               ogCellDataNotification,
               ogCellMessageNotification,
               ogCellSignalNotification,
               ogCellApnNotification,
               ogCellTowerNotification,
               ogCellNetworkNotification,
               ogWifiClientConnectNotification,
               ogWifiClientSignalNotification,
               ogWifiApAssociationNotification,
               ogWifiApAuthNotification,
               ogDialPoolHealthNotification,
               ogCustomNotification,
               ogCliUserSessionNotification
       }
       STATUS  current
       DESCRIPTION
               "A collection of notifications for the status system."
       ::= { ogStatus2Groups 3 }